Fluid flow and pressure
KT chillers fitted with a 2 or 3 litre per minute pump are capable of producing up to 150
psi, because of the high pressure volumetric pump. These units are normally supplied
factory set to run at an operating pressure of 35 psi, which is suitable for most applications.
The pressure setting is controlled by an internal bypass valve, which will open above the
preset level to protect your application from higher pressures.
It is possible for customers to change the operating pressure of all K series chillers, except
KT chillers fitted with a 6 litre/minute pump
1
. For details of this procedure, refer to the
technician section.
4.0 Maintenance requirements, Operator
Caution: Failure to carry out service at the specified intervals may permanently damage
your equipment. For maintenance and service requirements for technicians, and for
troubleshooting, refer to the technician section.
Exterior cleaning: Wipe up any spillages using a damp cloth only. Do not use detergents.
Interval Actions
Weekly Check fluid level
Check external connections for leaks
Annually Change the fluid
1
The 6 litre/minute pump is specially designed for low pressure applications, and the flow rate and pressure
settings cannot be changed on these units.