Technical information
IFD 244 · Edition 03.08
18
Parameters
Behaviour during start-up4.3
Normal start-up4.3.1
Parameter 22
The safety time t
SA
can be displayed or read on the type la-
bel.
t
W
t
1
3
5
9
4
7-8
*
L1
t
Z
t
SA
88
04
0201
Once the start-up signal (J) has been applied, the automatic
burner control unit checks the burner for flame simulation
during the waiting time t
W
. If no flame simulation is detected
during that period, the safety time on start-up t
SA
(3, 5 or 10 s)
then starts to elapse. This forms the minimum operating time
of the automatic burner control unit and the burner. Voltage is
supplied to the gas valve and ignition transformer. After the
safety time on start-up t
SA
has elapsed and the flame signal
has been received, the display shows the current program
status
04
.
Start-up without flame signal4.3.2
t
W
t
1
3
5
9
4
7–8
L1
t
Z
t
SA
ϑ
01
02
88
02
If, after a successful burner start, the automatic burner control
unit does not detect a flame signal during the safety time on
start-up t
SA
, a fault lock-out will occur (fault signalling contact
between terminals 7 and 8 closes). During the entire safety
time on start-up t
SA
, the gas valve V1 is open. The display
blinks and indicates
02
.