Specifications

28
Symptom Cause Remedy
1. Check power source.
2. Replace fuse(s).
3. Close or connect customer
interlock.
4. Switch to on position.
5. Close door.
6. Check stat and settings, reset
by re-cycling the power.
Check sensor and location.
7. Check for power at damper
motor and that end switch has
been wired correctly. End
switch should be wired N.O.
(normally open). Clear
linkage.
8. Reset the starter by pushing
red button on starter, check
amp draw.
9. Turn power off and check
belts.
10. Turn power off and check
motor and wiring.
11. Check time clock and field
installed controls for correct
settings and voltage.
12. Check night set back
thermostat for correct
settings.
13. Turn power off and check
bearings.
SECTION VII - TROUBLESHOOTING
A. Blower does not operate.
1. Low or no voltage.
2. Fuse(s) blown.
3. Customers interlock not
closed or connected.
4. Fan on-off switch in
off position.
5. Door switch open.
6. Freeze protection tripped.
7. Damper motor not operating,
its end switch not making, or
dampers binding.
8. Overload protection on
motor starter tripped.
9. Belts loose or broken.
10. Motor may be burned or
incorrectly wired.
11. Time clock or field installed
controls not closed.
12. Night set back thermostat
not closed.
13. Bearing seized on shaft.