Cut Sheet

NEMA 3, 3R, 4, 4X, 12
Plugs and Receptacles
Plugs and RecePtacles: ORdinaRy lOcatiOn
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© November 2011
812
WSR and WSRD Interlocked Receptacle
With Enclosed Disconnect Switch
600 Vac, 250 Vdc, 30, 60, 100 Amp, 50/60 Hz, Fused and Non-fused for use with Powertite
®
ACP and CPH plugs.
Amp
Wire Size
AWG Fusing
HP at 600
Vac Std/Max
3-Phase
Without
Viewing Window
With
Viewing Window
Aux. Contacts
1 or 2 NO/NC Mating Plug
Cast Aluminum Enclosure — NEMA 3, 3R, 4, 4X, 12
30 #14to#2
Fused 7.5/20 WSR3352 N/A WSAUX1 WSAUX2 ACP3034BC
Non-Fused 30 WSR33542 N/A WSAUX1 WSAUX2 ACP3034BC
60 #6to#2
Fused 15/50 WSR6352 N/A WSAUX1 WSAUX2 ACP6034BC
Non-Fused 60 WSR63542 N/A WSAUX1 WSAUX2 ACP6034BC
100 #4to#1/0
Fused 30/75 WSR10352 N/A WSAUX1 WSAUX2 ACP1034CD
Non-Fused 75 WSR103542 N/A WSAUX1 WSAUX2 ACP1034CD
Sheet Metal Enclosure — NEMA 3R, 12
30 #14to#2
Fused 7.5/20 WSRD3352SQ WSRD3352WSQ WSAUX1 WSAUX2 ACP3034BC
Non-Fused 30 WSRD33542SQ WSRD33542WSQ WSAUX1 WSAUX2 ACP3034BC
60 #6to#2
Fused 15/50 WSRD6352
N/A WSRDAUX1 WSRDAUX2 ACP6034BC
Non-Fused 60 WSRD63542
N/A WSRDAUX1 WSRDAUX2 ACP6034BC
Fused 15/50 WSRD6352SQ WSRD6352WSQ WSAUX1 WSAUX2 ACP6034BC
Non-Fused 60 WSRD63542SQ WSRD63542WSQ WSAUX1 WSAUX2 ACP6034BC
100 #4to#1/0
Fused 30/75 WSRD10352SQ WSRD10352WSQ WSAUX1 WSAUX2 ACP1034CD
Non-Fused 75 WSRD103542SQ WSRD103542WSQ WSAUX1 WSAUX2 ACP1034CD
Stainless Steel Enclosure — NEMA 3, 3R, 4, 4X, 12
30 #14to#2
Fused 7.5/20 WSRD3352N4SD WSRD3352N4WSD WSAUX1 WSAUX2 ACP3034BC
Non-Fused 20 WSRD33542N4SD WSRD33542N4WSD WSAUX1 WSAUX2 ACP3034BC
60 #6to#2
Fused 15/50 WSRD6352N4SD WSRD6352N4WSD WSAUX1 WSAUX2 ACP6034BC
Non-Fused 50 WSRD63542N4SD WSRD63542N4WSD WSAUX1 WSAUX2 ACP6034BC
100 #4to#1/0
Fused 30/75 WSRD10352N4SD WSRD10352N4WSD WSAUX1 WSAUX2 ACP1034CD
Non-Fused 75 WSRD103542N4SD WSRD103542N4WSD WSAUX1 WSAUX2 ACP1034CD
Square D Auxiliary Contacts for WSR/WSRD Disconnect Switch
Interlock Type 50 or 60 Hz Vac Make Break Cont. Vdc Make and Break Cont. Catalog Number
1NO/1NC
CONTACT
120 40A 15A 15A 115 0.50A 15A
WSAUX1
240 20A 10A 15A 230 0.25A 15A
480 10A 6A 15A
600 8A 5A 15A 600 0.05A 15A
2NO/2NC
CONTACTS
120 30A 3.0A 10A 115 1.0A 10A
WSAUX2
240 15A 1.5A 10A 230 0.30A 10A
480 7.5A .75A 10A
600 6.0A .60A 10A 600 0.10A 10A
Fuses not included in fused products. Class R fusing standard on WSRD fusible units and J Type on WSR. Product can be retrofitted with Class J, K, or S fusing.
‡ To order with auxiliary contacts installed, add suffix from this column to end of Catalog Number.
Standard Square D F-Series Disconnect Switch, except where noted.
Cutler Hammer Disconnect Switch. Cutler Hammer auxiliary switch is 1 NO/1 NC or 2 NO/2 NC.
Single pole single throw interlock kits are rated 1/2 HP @ 110 and 220 Vac. WSAUX1 utilizes a 9007A01 limit switch. WSAUX2 utilizes a 9007C03 limit switch.