Cut Sheet

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx nA nR IIC (Z2)
Class I, Zone 2, Ex nR IIC (Z) V
Class I, Zone 2, AEx nR IIC (ZB)
Class II, Division 1 and 2, Groups E, F, G
Class III
Simultaneous Exposure (Class I, Division 2/
Class II, Division 1)
Fixtures Outside Type (Salt Water)
Type 4X
IP66
Applications
• Enclosedandgasketedxturessuitableforusein:
—Marineandwetlocations
—Awiderangeofindustrial,chemicalprocessingandotherareas
whereammablegasesandvaporsorcombustibledustsare
presentunderconditionsdenedbytheNationalElectrical
CodeasClassI,Division2;ClassII,Division1and2;and
ClassIII
—Inapplicationsinvolvingmediumandhighmountingheights
—Inapplicationswhereenergyefcient,highlumenoutputis
required
—TheAExnAnRMercmasterIIIxtureisfactorysealedand
preventsvaporsandgasesfromenteringtheglobechamber.
Therearenosealsorputtyrequired.
—TheAExnRMercmasterIIIxturerequiresallwiringentriesto
besealed.
—Non-hazardouslocationswheresevereweatherconditions,
excessivemoisture,dirt,dust,corrosiveatmosphereorhigh
ambienttemperaturesareencountered
• Typicalapplicationsinclude:
—Pulpandpapermills
—Processingplants
—Chemicalplants
—Oilreneries
—Foundries
—Manufacturingplants
—Storageareas
—Wasteandsewagetreatment
—Otherareaswheredust,water,dirtandroughusagearea
problem
Features
• Superiorcorrosionresistance.
• Choiceoflightsources:highpressuresodium,andpulsestart
metalhalide.
• Sixmountingarrangementstosuitanylightinglayout:pendant,
ceiling,wallbracket,25°(angle)stanchion,90°(straight)
stanchionandcone.
• Hingehashighlipforaddedsafetyduringinstallationand
servicing.Hingeandboltconstructionassures360ºcompression
atallpointsonballasthousinggasketforpositivesealing.Swing
awaydesignofcaptiveboltandnutsimpliesservicing.
• Choiceofopticalassemblies:prismaticglobe;enclosedreec-
torwithsealedlens;orTypeVorTypeIIclosedprismaticglass
refractor,withorwithoutguards.
• Widechoiceofphotometricdistributions.
• Allxturesdesignedtoperformina104ºF/40ºCambienttemper-
ature.Selectedxturesaresuitableforambienttemperaturesup
to149ºF/65ºC.
• Mogulbaseporcelainlampholderwithnickel-platedcontacts
has392°F/200°Cratedweldedleads,pre-wiredtotheballast.
Assurestrouble-freeoperationininstallationswherehighambient
temperaturesareencountered.
• Forelectricalprotection,agroundwireisprovidedoneach
Mercmastertobondhoodandballasthousing.
• TerminalblocksareprovidedforZone2xturestofacilitatewiring.
• Standarddomeof30ºanglereectorsmadeofberglassrein-
forcedwhitepolyester.Highlyresistanttocorrosiveatmospheres.
• Awiderangeofvoltagesavailable(120to600Volt)andballast
types(CWA,CWIandSuperCWA).
• One-pieceballasthousingforeachcomponentprovideseven
heatdissipationforcooleroperationandlongerballastlife.
• AllMercmastermountinghoodshaveprovisionforeasyeldin-
stallationoffusesinxtures(seefusekitlistings).
Standard Materials
• Mountinghoodsandballastbodies:castcopperfree(lessthan
4/10of1%copper)aluminum
• Reectors:Fiberglassreinforcedwhitepolyester
• Guards,hardwareandcatchassemblies:stainlesssteel
• Globe:heat-andimpact-resistantinternallyutedglass
• Refractors:prismaticglass
• Enclosedreector:etchedAlzakaluminumwithsealed,tempered
heat-andimpact-resistantlens
• Bodyandglobegaskets:high-temperaturesiliconerubber
Standard Finishes
• Mountinghoodsandguards:epoxypowdercoat,electrostatically
appliedforcompleteanduniformprotection
Options
• AExnAnRxturesareavailablewithaClassI,Zone2rating.Add
sufx-Z2.
• AExnRxturesareavailablewithaClassI,Zone2rating.Add
sufx-ZB.
• ExnRxturesareavailablewithaClassI,Zone2rating.Add
sufx-Z V.
• QuartzAuxiliarycomestofullbrightnessimmediatelyand
remainslituntiltheHIDlampattains60-70%offullillumination.
QuartzAuxiliarysuppliedwithrelayswitchandsockettoaccept
120Vquartzdouble-contactbayonetbaselamp(notincluded).
(Notsuitableforhazardouslocations.)Addsufx-E.
• Factorysealedphotocontrolavailable.SeePCD2Series.
• SmartStarterincorporatesa1-1/2-minutetimerandperforms
asaconventionalstartertonormallystartlamp.Removes
itselffromcircuitiflampburnsoutorisremovedfromsocket.
Eliminatesstarterfailurescausedbyprolongedoperationwith
cyclingorfailinglampsandsimpliesndingtheirlocation,
reducingmaintenanceandrepaircosts.AvailableforallHPS
andPSMHxtures.Addsufx-S.
Certifications and Compliances
• ULStandard:UL1598,UL1598A,UL844,UL60079-0,UL
60079-15
• ULListed:E10444
Enclosed Reflector Prismatic Glass Globe 12” Glass Refractor
Lighting
Lighting: EncLosEd and gaskEtEd — arEa — hid
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
976
Mercmaster
III 400 Luminaire for Hazardous and Wet Locations
High Pressure Sodium and Pulse Start Metal Halide
Listed for si mul ta ne ous ex po sure to com bust i ble dusts and flam ma ble gas es or va pors.
V CSA Certification only.

Summary of content (2 pages)