Cut Sheet
LED Signals
Color Timing Description
Green 1secON:1secOFF
Normalchargingok,Batterynotyetfully
charged,Nofaultdetected,Testingok
Green 0.25secON:0.25secOFF Functional/DurationSelf-Teston-going
Green SteadyON
Chargingok,Batteryfullycharged,Nofault
detected,Testingok
Red 1secON:1secOFF
Faultcondition.Installationissue.Batteryis
reverse,notconnectedorshorted.
Functionaltestfailure,fullduration
testfailure
LEDIndicatorsOFF,LEDArrayON LEDIndicatorLights(RedandGreen)OFF NoAC,EmergencymodeON
Automatic Testing System (ATS)
Functional Full Duration
Startswithin24to45hoursaftertheinitialpowerupofthemodule Startswithin5to26daysaftertheinitialpowerofthemodule
Occursevery14daysaftertheinitialaforementionedfunctionaltest Occursevery364daysaftertheinitialaforementionedfunctionaltest
Lastsfor5minutes Lastsforthefulldurationoftheratedemergencyperiod
Atthecompletionoffunctionalandfulldurationtests,LEDindicatorwilldisplaythestatusoftheemergencyluminairewhenACispresent
LEDIndicator LEDArray
Industrial Mercmaster
™
LED Low Profile Luminaires with Emergency Battery Backup
For Ordinary Locations
NEC/CEC:
CCSAus Listed
Type 3R, 4, 4X
IP66/67
NEC/CEC:
Simultaneous Exposure
Suitable for Use in Wet Locations
American Bureau of Shipping (ABS) Certied
LED/ArEA: NEC/CEC EmErgENCy
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© September 2018
6