Cut Sheet

GBL: Grounding Insulated Bushing
Application
Used with a locknut to terminate rigid metal conduit or IMC
conduit to a box or enclosure.
Features
Threaded (NPS) for rigid conduit and IMC.
Temperature rating 150 °C.
Low surface friction permits pulling of wires with
virtually no abrasion on the cable insulation.
Set screw provided with each tting locks bushing in any
desired position.
For use with copper or aluminum grounding conductors.
Material/Finish
• Body: zinc
Lug: aluminum/tin plated
Clamping screw: steel/zinc plated
Set screws: steel/zinc plated
Certifications and Compliances
UL Standard: 467
UL Listed: E37337
CSA Standard: C22.2 No. 41
• CSA Certi ed: 208044
• NEMA: FB-1
C
B
A
GBL
Trade Size (Inches) Catalog Number
Dimensions in Inches/Millimeters
Wire Range
A
Bushing Diameter
B
Bushing Height
C
Turning Radius w/Lug
12 GBL-100 1.04/26.4 0.49/12.4 1.36/34.5 4-14
34 GBL-200 1.28/32.5 0.49/12.4 1.48/37.6 4-14
1 GBL-300 1.53/38.9 0.60/15.2 1.57/39.9 4-14
1-14 GBL-400 1.89/48.0 0.61/15.5 2.14/54.4 1/0-14
1-12 GBL-500 2.16/54.9 0.60/15.2 2.26/57.4 1/0-14
2 GBL-600 2.66/67.6 0.60/15.2 2.49/63.2 1/0-14
2-12 GBL-700 3.23/82.0 0.83/21.1 2.76/70.1 1/0-14
3 GBL-800 3.85/97.8 0.83/21.1 3.07/78.0 1/0-14
3-12 GBL-900 4.35/110.5 0.83/21.1 3.33/84.6 1/0-14
4 GBL-1000 4.87/123.7 0.83/21.1 3.57/90.7 1/0-14