EBR/DBR Receptacles 30, 60, 100 and 150 Amp
Circuit Breaker and Disconnect Switch Data
600 Vac Maximum.
EBR Shown
Solderless lugs are provided for
line connections, and receptacle is
prewired to the load side of breaker.
Cover-mounted components leave
entire enclosure space free for pulling
of line conductors and wiring.
EBR Shown
Plug is mechanically locked in
receptacle when circuit breaker is ON.
Design provides interlocked connect
and disconnect operation as well as
short circuit and thermal time delay
overload protection.
Breaker operating handle can be
padlocked in either ON or OFF
position and is trip-free.
Enclosure has additional 3/4”
threaded openings top and bottom
for installation of optional drain and
breather; reducers furnished.
EBR/DBR Horsepower Tables
These Cutler-Hammer
circuit breaker recommendations are for induction motors running with usual speed
and torque characteristics. Ambient temperature, and frequency of starting could require different protective
characteristics.
HP 120 Vac 240 Vac 480 Vac 600 Vac
EBR3023
DBR3023
(2W, 3P, 1-Phase,
30 Amp 2-Pole)
1 40EHD 20EHD 15EHD 15FDB
1-1/2 40EHD 30EHD 15EHD 15FDB
2 50EHD 30EHD 20EHD 15FDB
3 –– 40EHD 30EHD 20FDB
5 –– –– 40EHD 30FDB
7-1/2 –– –– 40EHD 40FDB
EBR6023
DBR6023
(2W, 3P, 1-Phase,
60 Amp 2-Pole)
3 50EHD –– –– ––
5 100EHD 50EHD –– ––
7-1/2 70EHD –– ––
10 –– –––– 50EHD 40FDB
EBR3034
DBR3034
(3W, 4P, 3-Phase,
30 Amp 3-Pole)
1 –– 15EHD 15EHD 15FDB
1-1/2 –– 15EHD 15EHD 15FDB
2 –– 20EHD 15EHD 15FDB
3 –– 30EHD 15EHD 15FDB
5 –– 40EHD 20EHD 20FDB
7-1/2 –– 50EHD 30EHD 30FDB
10 –– –– 40EHD 30FDB
15 –– –– 40EHD 40FDB
20 –– –– –– 50FDB
EBR6034
DBR6034
(3W, 4P, 3-Phase,
60 Amp 3-Pole)
10 –– 50EHD –– ––
15 –– 70EHD –– ––
20 –– –– 50EHD ––
25 –– –– 50EHD 50FDB
30 –– –– 70EHD 50FDB
40 –– –– –– 70FDB
EBR1034
DBR1034
(3W, 4P, 3-Phase,
100A and 150 Amp 3-Pole)
20 –– 100EHD –– ––
25 –– 100EHD –– ––
30 –– 150FD –– ––
40 –– –– 100EHD ––
50 –– –– 100EHD 100FDB
60 –– –– 125FD 125FDB
75 –– –– –– 125FDB
EBR/DBR Circuit Breaker Data — Cutler-Hammer
Frame
Continuous
Amp Max Volts
Interrupting Ratings (RMS SYM Amp)
240 Vac 480 Vac 600 Vac
EHD 20-100 480 18,000 14,000 ––
FDB 20-125 600 18,000 14,000 14,000
FD 20-150 600 65,000 25,000 18,000
EBR/DBR Horsepower Rating Table — Disconnect Switch
Max. Amp
Max. Horsepower Rating
120 Vac 240 Vac 480 Vac 600 Vac 250 Vdc
30 5 10 20 25 7-1/2
60 10 20 40 60 15
100 15 30 75 75 25
150 – 50 100 150 –