Cut Sheet

CodeMaster 2
HID Factory Sealed Luminaire Technical Data
Explosionproof, Dust-Ignitionproof
Integrally Ballasted. 50 W, 70 W, 100 W, 150 W, 250 W, 400 W HPS; 175 W, 250 W, 320 W, 350 W, 400 W PSMH; 175 W, 250 W, 400 W MH V.
Mogul Base. For use with threaded metal conduit.
“T” Numbers Represent the Maximum Surface Temperature for Class I, Division 1 Locations and
Maximum Surface Temperature Under Dust Blanket for Class II, Division 1 Locations.
“T”
Number T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp.
Range
(°F)
664-
842
619-
662
574-
617
538-
572
502-
536
448-
500
421-
446
394-
419
358-
392
331-
356
322-
329
277-
320
250-
275
214-
248
187-
12
185
Temp.
Range
(°C)
351-
450
326-
350
301-
325
281-
300
261-
280
231-
260
216-
230
201-
215
181-
200
166-
180
161-
165
136-
160
121-
135
101-
120
86-
100
85
NOTE: The maximum operating temperature of the fixture must not exceed the ignition temperature of the gas, vapor or dust to be encountered per the National
Electrical Code and the Canadian Electrical Code.
Applies to Code•Master 2 only.
V CSA Certification only.
Classified Area Suitability of Code•Master 2 Series HID Fixtures — Suitability includes use of reflector
Lamp
Type
Lamp
Watts
Supply Wire
(°F/˚°C)
Ambient Temp
(°F/°˚C)
Class I, Division 1 & 2 With Globe or with
Globe & Reflector UL/NEC/CEC Temp. Ident. No.
Class II, Division 1 & 2
With Globe or with Globe & Reflector
UL/NEC/CEC Temp. Ident. No.
Nameplate Marking
NEC
Groups
CEC V
Groups Nameplate Marking Groups
High
Pressure
Sodium
50 122/60 104/40 T6 C,D B,C,D T4 E,F,G
50 167/75 131/55 T5 C,D B,C,D
50 185/85 149/65 T5 C,D B,C,D
70 140/60 104/40 T6 C,D B,C,D T4 E,F,G
70 167/75 131/55 T5 C,D B,C,D
70 185/85 149/65 T5 C,D B,C,D
100 122/60 104/40 T5 C,D B,C,D T4 E,F,G
100 167/75 131/55 T5 C,D B,C,D
100 185/85 149/65 T4A C,D B,C,D
150 122/60 104/40 T5 C,D B,C,D T3A E,F
150 167/75 131/55 T4A C,D B,C,D T3
250 167/75 104/40 T3C C,D B,C,D
250 167/75 131/55 T3C C,D B,C,D
400 185/85 104/40 T3C C,D B,C,D
PulseStart
MetalHalide
175 167/75 104/40 T4 C,D B,C,D T3C E,F,G
250 167/75 104/40 T4 C,D B,C,D T3A E,F
320 167/75 104/40 T3C C,D B,C,D
350 167/75 104/40 T3C C,D B,C,D
400 167/75 104/40 T3C C,D B,C,D
MetalHalideV
175 167/75 104/40 T4 B,C,D T3C E,F,G
250 167/75 104/40 T4 B,C,D T3A E,F
400 167/75 104/40 T3C B,C,D
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
Marine Type Electric Fixtures
Outside Type (Salt Water)
CEC: V
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2; IIB, IIA
Class II, Division 1, Groups E, F, G
Class II, Division 2, Groups F, G
Class III
CSA Type 4X
Exd IIB, Zone 1
Lighting
Lighting: ExpLosionprooF — arEa — hid
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010