Cut Sheet

Photometric Data
Total Luminaire Efficiency = 57.4%
REPORT NUMBER: CMBF64AN
64 W (two 32 W lamps) Fluorescent Fixture with Globe and
30° Angle Dome Reflector *
CIE Type - Direct
Plane
Spacing
Criteria
Maximum Candela = 731
Located at
Horizontal
Angle = 90, Vertical Angle = 37.5
#1 – Vertical Plane through Horizontal Angles (90-270)
(Through Max. Cd.)
#2 – Horizontal Cone through Vertical Angle (37.5)
(Through Max. Cd.)
0-180 1.52 Coefficients of Utilization - Zonal Cavity Method
90-270 1.70 Effective Floor Cavity Reflectance 0.20
Diagonal 1.62 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens 0 68 68 68 68 67 67 67 67 64 64 64 61 61 61 58 58 58 57
0-10 62.13 1 61 58 55 52 59 56 54 51 54 51 49 51 49 48 49 48 46 45
10-20 187.93 2 55 49 45 41 53 48 44 40 46 43 39 44 41 39 42 40 38 36
20-30 317.49 3 50 43 37 33 48 42 37 33 40 36 32 38 35 32 37 34 31 30
30-40 428.14 4 45 37 32 28 44 37 31 27 35 31 27 34 30 27 32 29 26 25
40-50 471.22 5 41 33 28 23 40 32 27 23 31 27 23 30 26 23 29 25 22 21
50-60 454.23 6 38 30 24 20 37 29 24 20 28 23 20 27 23 20 26 22 19 18
60-70 384.77 7 35 27 21 18 34 26 21 18 25 21 17 24 20 17 24 20 17 16
70-80 276.31 8 32 24 19 16 32 24 19 15 23 19 15 22 18 15 22 18 15 14
80-90 157.68 9 30 22 17 14 29 22 17 14 21 17 14 20 16 14 20 16 13 12
90-100 13.45 10 28 20 16 12 28 20 15 12 19 15 12 19 15 12 18 15 12 11
100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 0.00 0-30 567.55 11.8 20.6 90-120 13.45 0.3 0.5
140-150 0.00 0-40 995.69 20.7 36.2 90-130 13.45 0.3 0.5
150-160 0.00 0-60 1921.14 40.0 69.8 90-150 13.45 0.3 0.5
160-170 0.00 0-90 2739.90 57.1 99.5 90-180 13.45 0.3 0.5
170-180 0.00 0-180 2753.35 57.4 100.0
Total Luminaire Efficiency = 67.2%
REPORT NUMBER: CMBF64DD
64 W (two 32 W lamps) Fluorescent Fixture with Globe and
Deep Dome Reflector *
CIE Type - Direct
Plane
Spacing
Criteria
Maximum Candela = 933
Located at Horizontal Angle = 0, Vertical Angle = 7.5
#1 – Vertical Plane through Horizontal Angles (0-180)
(Through Max. Cd.)
#2 – Horizontal Cone through Vertical Angle (7.5)
(Through Max. Cd.)
0-180 1.44 Coefficients of Utilization - Zonal Cavity Method
90-270 1.44 Effective Floor Cavity Reflectance 0.20
Diagonal 1.60 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens 0 80 80 80 80 78 78 78 78 75 75 75 71 71 71 69 69 69 67
0-10 88.95 1 73 70 67 65 71 68 66 63 66 63 61 63 61 60 60 59 58 56
10-20 260.61 2 66 61 56 52 65 59 55 52 57 53 50 55 52 49 53 50 48 47
20-30 413.34 3 60 53 47 43 59 52 47 43 50 45 42 48 44 41 46 43 40 39
30-40 539.82 4 55 47 41 36 53 46 40 36 44 39 35 42 38 35 41 37 34 33
40-50 630.36 5 50 41 35 31 49 41 35 30 39 34 30 38 33 30 37 33 29 28
50-60 641.74 6 46 37 31 26 45 36 30 26 35 30 26 34 29 26 33 29 25 24
60-70 436.60 7 43 33 27 23 41 33 27 23 32 27 23 31 26 23 30 26 22 21
70-80 164.84 8 40 30 24 20 38 30 24 20 29 24 20 28 23 20 27 23 20 19
80-90 47.37 9 37 28 22 18 36 27 22 18 26 21 18 26 21 18 25 21 18 16
90-100 1.92 10 34 25 20 16 34 25 20 16 24 19 16 24 19 16 23 19 16 15
100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 0.00 0-30 762.91 15.9 23.7 90-120 1.92 0.0 0.1
140-150 0.00 0-40 1302.73 27.1 40.4 90-130 1.92 0.0 0.1
150-160 0.00 0-60 2574.82 53.6 79.8 90-150 1.92 0.0 0.1
160-170 0.00 0-90 3223.63 67.2 99.9 90-180 1.92 0.0 0.1
170-180 0.00 0-180 3225.55 57.4 100.0
Code•Master
2 Emergency PLT Factory Sealed Luminaires
Explosionproof, Dust-Ignitionproof
* Photometric data is based on a fixture with two 32 W Compact Fluorescent PL-T lamps (2,400 lumens each). For candlepower values of fixtures with two 26 W PL-T lamps (1,800 lumens each),
multiply by 0.75. For Candlepower values of fixtures with two 42 W PL-T Lamps. (3,200 lumens each) multiply by 1.34.
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4X
Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water)
Suitable for use in Wet Locations
NFPA101, Life Safety Code
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© May 2019
494