Cut Sheet
Code•Master
™
2 Emergency PLT Factory Sealed Luminaires
Explosionproof, Dust-Ignitionproof
Photometric Data
Total Luminaire Efficiency = 79.8%
REPORT NUMBER: CMBF64G
64 W (two 32 W lamps) Fluorescent Fixture with Globe only *
CIE Type - Semi-Direct
Plane
Spacing
Criteria
Maximum Candela = 493
Located at Horizontal Angle = 0, Vertical Angle = 70
#1 – Vertical Plane through Horizontal Angles (0-180)
(Through Max. Cd.)
#2 – Horizontal Cone through Vertical Angle (70)
(Through Max. Cd.)
0-180 2.88 Coefficients of Utilization - Zonal Cavity Method
90-270 2.88 Effective Floor Cavity Reflectance 0.20
Diagonal 2.82 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens 0 90 90 90 90 85 85 85 85 76 76 76 68 68 68 60 60 60 57
0-10 17.70 1 76 70 65 60 71 66 61 57 58 54 51 51 48 45 45 42 40 36
10-20 61.05 2 67 58 51 45 63 55 48 42 48 43 38 42 37 34 36 32 29 26
20-30 132.44 3 60 49 41 35 56 46 39 33 40 34 29 35 30 26 30 26 23 20
30-40 236.78 4 54 43 34 28 50 40 32 26 35 28 23 30 25 21 26 21 18 15
40-50 336.66 5 49 37 29 23 46 35 27 22 31 24 19 26 21 17 23 18 15 12
50-60 421.68 6 45 33 25 19 42 31 23 18 27 21 16 23 18 14 20 16 12 10
60-70 485.34 7 41 29 22 16 38 28 20 15 24 18 14 21 16 12 18 14 10 8
70-80 517.29 8 38 26 19 14 36 25 18 13 22 16 12 19 14 10 16 12 9 7
80-90 513.72 9 35 24 17 12 33 23 16 11 20 14 10 17 12 9 15 11 8 9
90-100 468.70 10 33 22 15 11 31 21 14 10 18 13 9 16 11 8 14 10 7 5
100-110 352.77
110-120 200.85
Zonal Lumen Summary
120-130 73.54
Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 11.28 0-30 211.19 4.4 5.5 90-120 1022.32 21.3 26.7
140-150 1.12 0-40 447.97 9.3 11.7 90-130 1095.85 22.8 28.6
150-160 0.31 0-60 1206.31 25.1 31.5 90-150 1108.26 23.1 28.6
160-170 0.06 0-90 2722.64 56.7 71.1 90-180 1108.63 23.1 28.9
170-180 0.00 0-180 3831.28 79.8 100.0
Total Luminaire Efficiency = 66.5%
REPORT NUMBER: CMBF64ST
64 W (two 32 W lamps) Fluorescent Fixture with Globe and
Standard Dome Reflector *
CIE Type - Direct
Plane
Spacing
Criteria
Maximum Candela = 808
Located at Horizontal Angle = 0, Vertical Angle = 35
#1 – Vertical Plane through Horizontal Angles (0-180)
(Through Max. Cd.)
#2 – Horizontal Cone through Vertical Angle (35)
(Through Max. Cd.)
0-180 1.62 Coefficients of Utilization - Zonal Cavity Method
90-270 1.62 Effective Floor Cavity Reflectance 0.20
Diagonal 1.74 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens 0 79 79 79 79 77 77 77 77 74 74 74 71 71 71 68 68 68 66
0-10 73.25 1 72 69 66 63 70 67 64 62 64 62 60 62 60 58 59 58 56 55
10-20 220.57 2 65 59 54 50 63 58 53 49 55 52 48 53 50 47 51 48 46 45
20-30 368.60 3 59 51 45 41 57 50 45 40 48 43 40 46 42 39 44 41 38 37
30-40 505.61 4 53 45 38 34 52 44 38 33 42 37 33 40 36 32 39 35 32 30
40-50 603.19 5 49 39 33 28 47 39 33 28 37 32 28 36 31 28 35 31 27 26
50-60 638.42 6 45 35 29 24 43 34 29 24 33 28 24 32 27 24 31 27 23 22
60-70 497.24 7 41 32 25 21 40 31 25 21 30 25 21 29 24 21 28 24 20 19
70-80 226.17 8 38 29 23 19 37 28 22 18 27 22 18 26 22 18 26 21 18 17
80-90 57.98 9 35 26 20 16 34 26 20 16 25 20 16 24 19 16 23 19 16 15
90-100 1.64 10 33 24 18 15 32 24 18 15 23 18 15 22 18 15 22 17 14 13
100-110 0.00
110-120 0.00 Zonal Lumen Summary
120-130 0.00 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 0.00 0-30 662.42 13.8 20.7 90-120 1.64 0.0 0.1
140-150 0.00 0-40 1168.03 24.3 36.6 90-130 1.64 0.0 0.1
150-160 0.00 0-60 2409.64 50.2 75.5 90-150 1.64 0.0 0.1
160-170 0.00 0-90 3191.04 66.5 99.9 90-180 1.64 0.0 0.1
170-180 0.00 0-180 3192.68 66.5 100.0
* Photometric data is based on a fixture with two 32 W Compact Fluorescent PL-T lamps (2,400 lumens each). For candlepower values of fixtures with two 26 W PL-T lamps (1,800 lumens each),
multiply by 0.75. For Candlepower values of fixtures with two 42 W PL-T Lamps. (3,200 lumens each) multiply by 1.34.
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4X
Marine Type Electric Fixtures
NEC:
Outside Type (Salt Water)
Suitable for use in Wet Locations
NFPA101, Life Safety Code
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© May 2019
493