Cut Sheet
Total Luminaire Efficiency = 92.9%
REPORT NUMBER: CJBF32G
32 W Fluorescent Lamp with Globe only *
CIE Type - Semi-Direct
Plane
Spacing
Criteria
Maximum Candela = 265
Located at Horizontal Angle = 0, Vertical Angle = 77.5
#1 - Vertical Plane through Horizontal Angles (0-180)
(Through Max. Cd.)
#2 - Horizontal Cone through Vertical Angle (77.5)
(Through Max. Cd.)
0-180 2.76 Coefficients of Utilization - Zonal Cavity Method
90-270 2.76 Effective Floor Cavity Reflectance 0.20
Diagonal 2.72 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens
0
103 103 103 103 97 97 97 97 85 85 85 74 74 74 65 65 65 60
0-10 9.75
1
88 81 75 70 82 76 70 65 65 61 57 56 53 50 48 45 42 38
10-20 32.89
2
78 67 59 52 72 63 55 49 54 48 43 46 41 37 38 35 31 27
20-30 68.63
3
69 57 48 41 64 53 45 38 46 39 33 39 33 29 32 28 24 20
30-40 119.65
4
63 50 40 33 58 46 37 31 39 32 27 33 28 23 28 23 19 16
40-50 174.44
5
57 43 34 27 52 40 32 25 35 27 22 29 23 19 24 19 16 13
50-60 219.68
6
52 38 29 23 48 36 27 21 31 24 18 26 20 16 21 17 13 10
60-70 252.32
7
48 34 25 19 44 32 24 18 27 21 16 23 18 13 19 15 11 9
70-80 278.38
8
44 31 22 17 41 29 21 16 25 18 14 21 16 11 18 13 9 7
80-90 283.11
9
41 28 20 14 38 26 19 14 23 16 12 19 14 10 16 12 8 6
90-100 266.38
10
38 25 18 13 35 24 17 12 21 15 10 18 12 9 15 10 7 5
100-110 231.16
110-120 166.66 Zonal Lumen Summary
120-130 91.63 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 31.38 0-30 111.27 4.6 5.0 90-120 664.20 27.7 29.8
140-150 2.95 0-40 230.92 9.6 10.4 90-130 755.83 31.5 33.9
150-160 0.19 0-60 625.05 26.0 28.0 90-150 790.17 32.9 33.9
160-170 0.00 0-90 1438.87 60.0 64.5 90-180 790.36 32.9 35.5
170-180 0.00 0-180 2229.23 92.9 100.0
Total Luminaire Efficiency = 80.7%
REPORT NUMBER: CJBF32ST
32 W Fluorescent Lamp with Globe and Standard Dome Reflector *
CIE Type - Direct
Plane
Spacing
Criteria
Maximum Candela = 545
Located at Horizontal Angle = 0, Vertical Angle = 5
#1 - Vertical Plane through Horizontal Angles (0-180)
(Through Max. Cd.)
#2 - Horizontal Cone through Vertical Angle (5)
(Through Max. Cd.)
0-180 1.42 Coefficients of Utilization - Zonal Cavity Method
90-270 1.42 Effective Floor Cavity Reflectance 0.20
Diagonal 1.60 % Ceiling Rcc 80 70 50 30 10 0
% Walls Rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
Zone Lumens
0
96 96 96 96 93 93 93 93 89 89 89 85 85 85 82 82 82 80
0-10 51.88
1
87 84 80 77 85 82 78 76 78 75 73 75 73 71 72 70 68 67
10-20 151.03
2
79 72 67 62 77 71 66 61 68 63 60 65 61 58 62 59 57 55
20-30 240.04
3
72 63 56 51 70 62 55 50 59 54 49 57 52 48 54 51 47 45
30-40 312.02
4
65 55 48 42 63 54 47 42 52 46 41 50 45 41 48 44 40 38
40-50 361.09
5
60 49 41 36 58 48 41 36 46 40 35 44 39 35 43 38 34 32
50-60 377.88
6
55 44 36 31 53 43 36 31 41 35 30 40 34 30 39 34 30 28
60-70 278.20
7
51 39 32 27 49 39 32 27 37 31 27 36 30 26 35 30 26 24
70-80 119.22
8
47 36 29 24 46 35 28 24 34 28 23 33 27 23 32 27 23 21
80-90 23.81
9
44 33 26 21 43 32 26 21 31 25 21 30 25 21 29 24 21 19
90-100 0.68
10
41 30 23 19 40 30 23 19 29 23 19 28 23 19 27 22 19 17
100-110 4.48
110-120 6.82 Zonal Lumen Summary
120-130 5.50 Zone Lumens % Lamp % Fixture Zone Lumens % Lamp % Fixture
130-140 3.07 0-30 442.95 18.5 22.9 90-120 11.98 0.5 0.6
140-150 0.09 0-40 754.97 31.5 39.0 90-130 17.48 0.7 0.9
150-160 0.00 0-60 1493.95 62.2 77.2 90-150 20.63 0.9 0.9
160-170 0.00 0-90 1915.18 79.8 98.9 90-180 20.63 0.9 1.1
170-180 0.00 0-180 1935.81 80.7 100.0
* Photometric data is based on a xture with
a 32 W compact uorescent PL-T lamp (2,400
lumens). For candlepower values of xtures
with 26 W PL-T lamps (1,800 lumens), multiply by
0.75. For candlepower values of xtures with a
42 W PL-T Lamp (3,200 lumens), multiply by 1.34.
Code•Master
™
PLT Factory Sealed Luminaire Photometric Data
Explosionproof, Dust-Ignitionproof
Integrally Ballasted. 26 W, 32 W, 42 W, 52 W, 64 W, 84 W Compact Fluorescent. For use with Threaded Metal Conduit.
Lighting
Lighting: ExpLosionproof — ArEA — fLuorEscEnt
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© January 2011
1248