Cut Sheet
Mounting Hoods
Hub Size
(Inches)
Catalog
Number
Pendant
3/4 CAP-75
1 CAP-100
Ceiling
3/4 CAC-75
1 CAC-100
Bracket
3/4 CALB-75
1 CALB-100
25° Stanchion
1-1/4or1-1/2➊ CAS-150 ➊
Mounting Adapter with Connection Block
CMAD-1
Fixture Units
Line
Voltage
Hz
Catalog
Number
Ballast body with globe
26-42 W
52-84 W
120-277 50/60
CJB26FBU ➋
120-277 50/60
CJB32FBU ➋
120-277 50/60
CJB42FBU ➋
120-277 50/60 CMBF52BU
120-277 50/60 CMBF64BU
120-277 50/60 CMBF84BU
Electrical Specification
Lamp Wattage Line Voltage Frequency (Hz) Line Amps Input Watts Min. Starting Temp
26(1x26) 120-277 50/60 0.25-0.11 28 0°F/-18°C
32(1x32) 120-277 50/60 0.27-0.12 36 0°F/-18°C
42(1x42) 120-277 50/60 0.35-0.16 48 0°F/-18°C
52(2x26) 120-277 50/60 0.49-0.20 55 -22°F/-30°C
64(2x32) 120-277 50/60 0.57-0.24 67 -22°F/-30°C
84(2x42) 120-277 50/60 0.73-0.31 87 -22°F/-30°C
➊ 1-1/2” tapped hub furnished with 1-1/2” to 1-1/4” reducer.
➋ Denotes items that are suitable for Class I, Group B in addition to Class I, Groups C and D; and Class II, Groups E, F and G.
V CSA Certification only.
Shaded items are suitable for Class I, Group C in addition to Class I, Group D; Class II, Groups E, F and G; and Class III.
Code•Master
™
PLT Factory Sealed Luminaire Mounting Hoods and Fixture Units
Explosionproof, Dust-Ignitionproof
Integrally Ballasted. 26 W, 32 W, 42 W, 52 W, 64 W, 84 W Compact Fluorescent. For use with Threaded Metal Conduit.
NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4X
Suitable for use in wet locations
CEC: V
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, Groups IIB + H
2
T6
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA 4X
Exd IIB + H
2
Suitable for use in wet locations
Lighting
Lighting: ExpLosionproof — ArEA — fLuorEscEnt
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.