Cut Sheet
Code•Master
™
PLT Factory Sealed Luminaires
Explosionproof, Dust-Ignitionproof
Integrally Ballasted. 26 W, 32 W, 42 W, 52 W, 64 W, 84 W Compact Fluorescent. For use with Threaded Metal Conduit.
Applications
• Foruseinhazardouslocationssuchasplantswhereplastics,
paints,thinnersandpetrochemicalsaremanufactured,andin
otherareaswhereignitablevapors,dust,moistureandcorrosive
elementsmaybepresent.
• Foruseinareaswhereaninstant-onwhitelightisdesired.
• Suitableforuseinwetlocations.
• Standardxturesdesignedfor26W,32W,42W,52W(two26
W),64W(two32W),and84W(two42W)PLTlamps.
• Coldweatherstartingtoaminimumtemperatureof0°F/
-18°CfortheCode•MasterJr.PLTand-22°F/-30°Cforthe
Code•Master2PLT.
Features
• Fixturesoperatesafelyinhighambienttemperatures.
• Arrangementofheat-producingcomponentsresultsinefcient
heatdissipationforcoolerxtureoperation.
• Patented“wireless”design.Threadingofxtureunitonto
mountinghoodmakeselectricalconnection.Theonly
wiringrequiredisattachingtwowirestoconnectionblock
inmountinghood.
• Connectionblockiseasilywired:(a)loosentwoscrews;(b)
makewireconnections;and(c)repositionconnectionblock.
• Safe,easyservicingwithoutdisconnectinganywiring.
“Wireless”xtureunitthreadsoffmountinghoodforconvenient
servicingorforimmediatereplacementwitha“stand-by”unit.
• Acmedouble-leadthreadsspeedinstallationandxtureremoval
frommountinghood–onlyhalfasmanyturnsarerequired
asforsingle-leadthreads.Thethreadsdonotstick,orgall,
eliminatingproblemsoftenencounteredwithsingle-leadthreads
duringxtureunitremoval.
• Allthreadedjointsareame-tight.
• Factorysealed.ExternalsealsnotrequiredforGroupsCandD.
• FixturesforuseinGroupBlocationsarefurnishedcomplete
withULrequiredsealingttingforCode•MasterJr.PLTonly.
• Heat-andimpact-resistantglobeshavesmooth
dust-resistantexterior.
• Superiorcorrosionresistance,withepoxypowdercoatnish.
• Fluorescentlightsourcereducesenergycost.
• Strategiclocationoflampsocket,incombinationwithinterior
prismdesignoftheglassglobe,providesoptimumlight
distributionandcontrol.
• Choiceofmountings–pendant,ceiling,bracketandstanchion.
• Optionalguardsprotectglobesfromdamage.Securedtoxture
withthreestainlesssteelscrews.
• Fiberglassreinforcedpolyesterreectors,instandarddome
or30°anglestyles,areidealininstallationswhereluminaireis
subjecttoexceptionallyseverecorrosiveatmospheres.The
highbayaluminumreectorisintendedforinstallationswhere
mountingheightworkplanesrangefrom20to30feet/6to9
meters.
• Fluorescentlamplifeof10,000hoursreducesrelampingcost
comparedtoincandescent,andprovidessuperiorTnumbers.
Standard Materials
• Ballastbodiesandguards:copperfree(4/10of1%max.)
aluminum
• Pendantmountinghoods:diecastcopperfree(4/10of1%max.)
aluminum
• Ceiling,bracketandstanchionmountinghoods:sandcast
copperfree(4/10of1%max.)aluminum
• Reectors:berglassreinforcedpolyester(white)or
aluminum
Standard Finishes
• Ballastbodies,guardsandmountinghoods:epoxypowder
coatnish,electrostaticallyappliedforcomplete,uniform
corrosionprotection
Certifications and Compliances
• ULStandard:UL1598,UL844
• ULListed:E10444
26-42W
Code•Master Jr. PLT
52-84W
Code•Master 2 PLT
Illustrated Features
Collector Ring
and Pin
Mounting Hood
Connection Block
Double Lead
Acme Threads
As Fixture unit is threaded into mounting
hood an automatic electrical connection is made.
Fixtures are for use with Group B atmospheres only when used with Group B mounting hoods. For 26 W,32 W, and 42 W fixtures only.
V CSA Certification only.
Lighting
Lighting: ExpLosionproof — ArEA — fLuorEscEnt
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© January 2011
1240
NEC:
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4X
Suitable for use in wet locations
CEC: V
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, Groups IIB + H
2
T6
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA 4X
Exd IIB + H
2
Suitable for use in wet locations