Cut Sheet
Classified Area Suitability of Code•Master 2 Emergency Series (Suitability includes use of reflector)
Lamp 
Type
Lamps 
Watts
Ambient 
Temp ˚ 
°C (°F)
Class I, Division 1 and 2 
With Globe or with Globe and Reflector 
UL/NEC Temp. Ident. No.
Class II, Division 1 and 2 
With Globe or with Globe and Reflector 
UL/NEC Temp. Ident. No.
Nameplate 
Marking Groups
Nameplate 
Marking Groups
PLT
52 40 (104)
T6 C, D T4 E, F, G
64 40 (104)
T6 C, D T4 E, F, G
84 40 (104)
T6 C, D T4 E, F, G
“T” Numbers Represent the Maximum Surface Temperature for Class I, Division 1 Locations and 
Maximum Surface Temperature Under Dust Blanket for Class II, Division 1 Locations.
“T” 
Number
T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp. 
Range 
(°˚C)
351-
450
326-
350
301-
325
281-
300
261-
280
231-
260
216-
230
201-
215
181-
200
166-
180
161-
165
136-
160
121-
135
101-
120
86-100 85
Temp. 
Range 
(°F)
664-
842
619-
662
574-
617
538-
572
502-
536
448-
500
421-
446
394-
419
358-
392
331-
356
322-
329
277-
320
250-
275
214-
248
187-
212
185
Fixture and Accessory Weights in kg (lb)
Fixture Size Fixture Weight Reflector Weight Guard Weight
52 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
64 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
84 W 20.4 (44.97) 1.4 (3.09) 0.9 (1.98)
Mounting Hood Weights kg (lb)
Pendant Ceiling Bracket Stanchion
0.9 (1.98) 1.8 (3.97) 2.7 (5.95) 0.9 (1.98)
Code•Master
™
 2 Emergency PLT Factory Sealed Luminaires
Explosionproof, Dust-Ignitionproof
52 W, 64 W, 84 W Fluorescent. For Use with Threaded Metal Conduit.
NEC: 
Class I, Division 1 and 2, Groups C, D 
Class II, Division 1 and 2, Groups E, F, G 
Class III 
NEMA 4X 
Marine Type Electric Fixtures 
NEC: 
Outside Type (Salt Water) 
Suitable for use in Wet Locations 
NFPA101, Life Safety Code
Electrical Specification for AC Operation
Fixture 
Wattage
Line 
Voltage (V)
Frequency 
(Hz)
Type of 
Ballast
Line 
Amps (A)
Maximum Wattage 
(W/W)
Catalog 
Number ˚
52 120 60 PLT Electronic 0.49 52 CMBFS5212
52 277 60 PLT Electronic 0.20 52 CMBFS5227
64 120 60 PLT Electronic 0.57 64 CMBFS6412
64 277 60 PLT Electronic 0.24 64 CMBFS6427
84 120 60 PLT Electronic 0.73 84 CMBFS8412
84 277 60 PLT Electronic 0.31 84 CMBFS8427
 For optional fusing, order kit -CF2.
FLUORESCENT/AREA: NEC/CEC EXPLOSIONPROOF
Visit our website at www.emerson.com or contact us at (800) 621-1506. 
© May 2019
488