ION App
The ION App™ enables remote viewing for appION™
Wireless Digital Gauges.
Reaching a Desired Measurement: In the ALARM
subview, set the Low Alarm to the desired micron
level. Select OK-Save.
Blank Off Leak Test: Isolate the system from the
vacuum pump and the evacuation connections.
In the ALARM subview, set the High Alarm to the
maximum desired micron level (eg. 500 microns).
Select OK-Save.
Monitor Evacuation Speed: To monitor how
quickly an evacuation is proceeding select the Rate
of Change subview. If the RoC displays as STABLE,
the evacuation has stalled and the oil may need to
be changed.
Adjust for Elevation: In the Navigation Menu, select
Settings, and then select Location Preferences.
Turn ON Account for Elevation and adjust settings
accordingly.