TM OPERATION MANUAL ⚠ WARNING TO REDUCE THE RISK OF INJURY OR PRODUCT DAMAGE, READ OPERATION MANUAL PRIOR TO OPERATING PRODUCT. PATENT PENDING - COPYRIGHT © 2014 - APPION INC.
Introduction AC/R system operating efficiency depends on proper evacuation - and proper evacuation depends on a reliable vacuum gauge capable of monitoring the entire evacuation process. The AV760 accurately displays measurements from atmosphere (760,000 microns) all the way to deep vacuum (10 microns), so you can be sure your system is clean, dry and tight. Table of Contents Safety.......................................................................3 Display & Controls ..................................
Safety • • • • Do not connect to systems under pressure. Do not use leaky or damaged batteries. Use only specified batteries and cleaning agents. Battery operating temperatures may vary by manufacturer. The batteries supplied with this unit are for storage and operating between 32ºF-104ºF (0ºC-40ºC). • Dispose of batteries in accordance with any applicable local laws and regulations. • Do not dispose of the product or battery in a fire or heat above 100ºC.
Display 1 2 3 4 5 1- Battery Indicator 2- Auto Power Off 3- Bluetooth Status 4- Measurement 5- Units Controls Press Backlight Power ON Hold Units Power OFF Both Toggle APO Timer Connect BT 1. Press a button for the “Press” function above. 2. Hold a button for 1 second for the “Hold” function. 3. Press both Backlight and Power to toggle Auto Power Off (APO) timer feature. 4 AV760 OPERATION MANUAL © 2014 APPION INC.
Using the AV760 CAUTION: Do not connect the AV760 to systems under high pressure. While the AV760 is designed to withstand accidental exposure to positive pressures, continued exposure may cause permanent damage. 1. Using the Appion Swivel Vacuum Connector (included), connect the AV760 to an available service port furthest from the vacuum pump. 2. Hand-tighten the connections to ensure a tight connection. Never tool-tighten a knurled fitting. 3. Press the Power button to turn on the AV760.
Bluetooth Operation NOTE: Bluetooth communication requires a compatible device running the ION App. Development of the ION App is ongoing, and any information presented in this manual about the ION App may not be up to date. Visit www.AppionTools.com or your device’s App Store for the latest ION App and additional information. 1. With the AV760 powered on, press and hold the “SYNC” button for a few seconds, until the Bluetooth symbol begins flashing on the AV760 screen. 2.
ION App The ION App™ enables remote viewing for appION™ Wireless Digital Gauges. Reaching a Desired Measurement: In the ALARM subview, set the Low Alarm to the desired micron level. Select OK-Save. Blank Off Leak Test: Isolate the system from the vacuum pump and the evacuation connections. In the ALARM subview, set the High Alarm to the maximum desired micron level (eg. 500 microns). Select OK-Save.
Maintenance The AV760 is a precision instrument and must be maintained to ensure proper functions. If the AV760 sensors get dirty and no longer read correctly, the Sensor Housing can be removed to enable easy cleaning of the sensors. 1. Remove the fitting, o-ring, and the oil catch filter from the sensor housing. WARNING: Do NOT remove the protective screen covering the sensor. 2. Apply Isopropyl Alcohol (70% or higher) to the sensor ports and flush the sensor ports for 5 minutes (page 9).
Tip: Use every precaution to check the oil catch filter periodically to ensure there is no oil buildup and to prevent gross leaks. 6. Replace the fitting onto the sensor housing port and hand-tighten. Never tool-tighten a knurled fitting. 7. Connect the AV760 to a vacuum pump, and run the pump until display reads 100 microns or less. ⚠ NOTICE Do not insert any objects into the sensor ports. Doing so may permanently damage the sensors. 9 AV760 OPERATION MANUAL © 2014 APPION INC.
Technical Information Measuring Range Accuracy Resolution Refresh Rate Units Power Battery Life 760,000 to 1 micron ± 5% ± 10 microns (1 to 5,000) ± 5% (5,000 to Atmosphere) 1 micron (1-499), 5 (500-2,000), 50 (2,000 - 5,000), 250 (5,00015,000), 1,000 (15,000 and up) <0.5 seconds Microns, mTorr, kPa, mBar, in/Hg, psia 3x AA Batteries 120 hours (continuous usage with radio turned off) Weight 5.9 oz (168.4 grams) Dimensions 4.86” x 2.86” x 1.
Regulatory Information This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. Federal Communication Commission Interference Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
Regulatory Information FCC Radiation Exposure Statement This equipment complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. FCC Caution To assure continued compliance, any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
AV760 OPERATION MANUAL © 2014 APPION INC.
Warranty Information Appion Inc. (hereinafter Appion) warrants that this equipment will, under normal and anticipated use, be free from defects in materials and workmanship for a period of one (1) year from the date of purchase by Purchaser from an Appion-authorized distributor. The complete Manufacturer’s Limited Warranty is available online at www. AppionTools.com All warranty services must receive Appion Factory Authorization and an RGA number prior to any action.