Product guide
page
17
DISCOVERY MOUNTING BASES
An earth connection is not
required for either safety or
correct operation of
detectors. The ground (earth)
terminal is isolated and is
provided for tidy termination
of grounded conductors or
cable screens and to
maintain earth continuity
where necessary.
All terminals are marked
according to their function.
Bases have a wide interior
diameter for ease of access
to cables and terminals and
there are two slots for fixing
screws. The slots enable two
fixing screws to be located
at a spacing of 51 to 69mm.
Detectors fit into bases one
way only, without snagging,
and require clockwise
rotation without push force
to be plugged in.
Universal patented address
cards, known as XPERT
cards, are supplied with all
bases. Consult the coding
guide in the installation
instructions to determine
which pips are to be
removed from the card to
give the correct address. Lay
the card on a flat surface, pips
down, insert a screwdriver
into the slot on the reverse
of the pip to be removed
and give a firm twist.
When the card is coded
insert it into the slot in the
side of the appropriate base,
making sure that the card
locks itself into place. As a
detector is inserted into the
base, the remaining pips
operate the address buttons
on the detector and the
detector electronics reads
the address.
Discovery/XP95 Mounting Base ▲ Part Number 45681-210 with XPERT card
TECHNICAL
DESCRIPTION
All detectors in the
Discovery range fit into
XP95 mounting bases.
Full details of bases and
mounting accessories are
given in PP1089 and PIN
sheets PP2040 and 2043.
The bases are of 100mm diameter and have five
terminals:
L1 line in and line out double terminal
L2 line in and line out double terminal
–
R remote LED negative supply double terminal
+R remote LED positive supply double terminal
E earth single terminal