Product Overview

AE Actuator
General
Specifications
26
Actuator Breakaway Torque Cycle Time Duty Cycle Amperage Draw (max.)
Model Output
(in.-lbs.) 90˚ Travel Starting or locked rotor current voltage
(50% Load) 115 VAC 230 VAC 12 VDC 24 VDC
AE200 200 in-lbs 5.0 sec. 25% .74 amp .44 amp 1.6 amp 1.7 amp
AE400 400 in-lbs 10.0 sec. 25% .74 amp .44 amp 1.6 amp 1.7 amp
AE600 600 in-lbs 15.0 sec. 25% .74 amp .44 amp 1.6 amp 1.7 amp
AE800 800 in-lbs 20.0 sec. 25% .74 amp .44 amp 1.6 amp 1.7 amp
AE1000 1000 in-lbs 25.0 sec 25% .74 amp .44 amp 1.6 amp 1.7 amp
Note: 90˚ Travel = Travel From Closed position to Open position or vice versa.
DC current draw is at max. torque
24 VAC current draw at locked rotor 4.6 amp
Motor AC models: 120 VAC or 230 VAC, Reversible 3 wire, capacitor run. Self-resetting
(thermal) overload protection, Class B insulation, sub-fractional horsepower.
DC models: 12 VDC or 24 VDC, Reversible 2 wire, POS & NEG. No thermal overload
(external circuit breaker or fuse suggested for protection.)
Lubrication Permanently lubricated gear train and bearings
Duty Cycle The AE-Series actuators are designed to operate at 25% duty cycle at temperatures
below 100˚F.
See Electrical Operation.
(24 AC-20% duty cycle below 100˚F)
Temperature Operating 32˚F to 150˚F Max
Range -40˚F to 150˚F with optional heater & thermostat
Thermal Protection Self-resetting (AC Motors Only)
Conduit Connections (2) 1/2”-NPT female
Direction Of Travel Clockwise to Close, Counterclockwise to Open (Position indicator shaft only, manual
override shaft rotates opposite)
AE Dimensions
Actuators and Controls