Brochure

For additional information, submittal sheets and manuals, visit www.apollovalves.com
APOLLO VALVES Customer Service (704) 841-6000
62
www.apollovalves.com
INSTALLATION GUIDE & PRESSING INSTRUCTIONS
MINIMUM SPACING
Between APOLLOXPRESS® Joints
To prevent distortion of the pipe, ttings require a minimum distance
between ttings (refer to chart below). Failure to provide this distance
may result in an improper seal.
Fitting Size
Minimum Spacing
½” 0”
¾” 0”
1” 0”
1 ¼” ½”
1 ½” ⁄”
Fitting Size
Minimum Spacing
2” ¾”
2 ½” ⁄”
3” ⁄”
4” ⁄”
Between an APOLLOXPRSS® Joint and Existing Solder Joint
The minimum distance when making an APOLLOXPRESS® joint near
a solder joint is in the table below. No residual solder, ux, or debris
should be on the tubing.
Tube Dia. Minimum Distance
½” ¼”
¾” ¼”
1” ⁄”
1 ¼” ⁄”
1 ½” ⁄”
Tube Dia. Minimum Distance
2” ¾”
2 ½” ¼”
3” ¼”
4” ¼”
Between an APOLLXPRESS® Joint and Existing Brazed Joint
The minimum distance when making an APOLLOXRESS® joint near a
brazed joint is 2 pipe diameters of the tube being pressed.
Tube Dia. Minimum Distance
½” 1”
¾” 1 ½”
1” 2”
1 ¼” 2 ½”
1 ½” 3”
Tube Dia. Minimum Distance
2” 4”
2 ½” 5”
3” 6”
4” 8”
When Soldering near an APOLLOXPRESS® Joint
Minimum distance is found in the table below. The installer shall take
proper precautions to protect and keep cool the APOLLOXPRESS® joint
using one of the following methods.
Wrap joint in a cold wet rag.
Use a spray type spot freezing product. The product should NOT
come into contact with the joint.
Prefabricate the solder connection, waiting for it to cool and then
make the press connection.
Tube Dia. Minimum Distance
½” 1 ½”
¾” 2 ¼”
1” 3”
1 ¼” 3 ¾”
1 ½” 4 ½”
Tube Dia. Minimum Distance
2” 6”
2 ½” 7 ½”
3” 9”
4” 12”
When Brazing near an APOLLOXPRESS® Joint
Stay at least 12 inches away from the pressed connection. The
installer shall take proper precautions to protect and keep cool the
APOLLOXPRESS® joint using one of the following methods.
Wrap joint in a cold wet rag.
Use a spray type spot freezing product. The product should NOT
come into contact with the joint.
Prefabricate the brazed connection, waiting for it to cool and then
make the press connection.