Brochure
For additional information, submittal sheets and manuals, visit www.apollovalves.com
APOLLO VALVES Customer Service (704) 841-6000
38
www.apollovalves.com
58A SERIES
Balancing Valve
DESCRIPTION:
Apollo Model 58A balance valves are precision engineered and
manufactured valves which provide two position hydronic circuit
isolation capability and multi-turn throttling adjustment as
required for proportional balancing of hydronic systems. The
valves unique needle valve adjustment, with integrated digital
readout incorporated into the handle allows qualied technicians
to have the valve function as a highly accurate variable orice
ow meter. Valve pressure drop can be read through the valves
integrated 1/4” measurement ports, and ow calculated from
the ow coecient associated with the numerical setting.
FEATURES:
• P/T plugs
• Compatible with All Flow Meters
• Easy Adjustment and Setpoint Indicator
• Isolated Flow Shut-o
• Reversible Lever
PERFORMANCE RATING:
• Max Pressure: 600 psi (41.3 bar)
• Max Temp: 250°F (121°C)
MATERIAL SPECIFICATIONS:
Part Name Material
Valve Body DZR brass CW602N
Ball & Needle
DZR brass CW602N (chrome plated)
Valve Handle Glass Filled Polyamide
Sealing O-ring EPDM
Gasket PTFE
Test Port Seal EPDM
DIMENSIONS IN
Part
Number
Size C
v
A B C D E F
Wt
(lbs.)
58A103PR 1/2” 1.66 2.7 3.5 3 5 3.9 1.1 1.1
58A104PR 3/4” 4.51 2.9 3.7 3 5.2 4.6 1.34 1.4
58A105PR 1” 8.18 3.2 4 3.2 4.5 5.7 1.61 1.8
58A106PR
1-1/4”
13.89
3.5 5.4 4.3 7.8 6.4 1.97 3.3
58A107PR
1-1/2”
23.9 3.7 5.7 4.4 8.3 7.0 2.24 4.3
58A108PR 2”
33.77
4.2 6.3 4.7 8.8 7.9 2.76 6.0
For liquids the ow coecient - C
v
- expresses the ow capacity in gallons per minute
(GPM) of 60°F water with a pressure drop of 1 psi (lb/in2).
OPTIONS
Solder Connection (58A-S Series)
Press Connection (58A-PR Series)
Push Connection (58A-P Series)
APPROVED APPLICATIONS:
Hot Water & Chilled Water low temperature hydronic HVAC
system adjustment.
Not intended for potable water