Specifications

16201-14
L:\wpb_\wpb_emp1\W1200.13\p.m. Project #1\SECTION 16201-Indoor Generator and ATS.doc
1. Iron
2. Chromium
3. Copper
4. Aluminum
5. Silicon
6. In addition the sample shall be tested for the presence of water, fuel
dilution, and antifreeze.
B. All equipment needed to take oil samples shall be provided in a kit at the
time of acceptance and shall include the following:
1. Sample gun kit (1)
2. Bottles (4)
3. Mailers (4)
4. Written instructions (1)
C. Immediate notification shall be provided to the Owner when analysis
results shows any critical reading. If readings are normal, a report stating
that the equipment is operating within established requirements shall be
provided.
D. This scheduled oil sampling program shall be made available to the Owner
beyond the mandatory one (1) year specified above and shall be optional
for the Owner to continue that program after that time period has elapsed.
3.06 TRAINING
A. Provide training of ATS and generator systems.
B. Provide a minimum of 4 hours training. Training shall be at a time
convenient to the Owner.
C. Operation and maintenance training shall be provided.
END OF SECTION