Specifications
16201-9
L:\wpb_\wpb_emp1\W1200.13\p.m. Project #1\SECTION 16201-Indoor Generator and ATS.doc
Low oil pressure
ALARM
Oil pressure sender failure
Low coolant temperature
High coolant temperature
Engine temperature sender failure
Low DC voltage
High DC voltage
Weak battery
Low fuel-daytank
Ground fault
Over load
Low coolant level
Low oil pressure (shutdown)
SHUTDOWN
High coolant temperature (shutdown)
Fail to crank (shutdown)
Fail to start/overcrank (shutdown)
Overspeed (shutdown)
High AC voltage (shutdown)
Low AC voltage (shutdown)
Under frequency (shutdown)
Over current (shutdown)
Short circuit (shutdown)
Emergency stop (shutdown)
Low coolant level
Over current (warning)
WARNING
2. Provide form “A” contacts for each of the above to be used in
SCADA system.
3. Provide common fault alarm.
D. Unit shall work with ATS. All labor and material shall be provided to
coordinate the installation with the ATS.
2.07 GENERATOR RATINGS
A. The size of the generator shall be 350 kW or as minimally indicated in the
drawings and be rated .8 PF. Increase generator size as may be required.
All loads are considered fully loaded.