Specifications
16201-5
L:\wpb_\wpb_emp1\W1200.13\p.m. Project #1\SECTION 16201-Indoor Generator and ATS.doc
B. The generator shall be capable of delivering rated output (kVA) at rated
frequency and power factor at any voltage not more than 5 percent above
or below rated voltage.
C. A permanent magnet generator (PMG) shall be included to provide a
reliable source of excitation power for optimum motor starting and short
circuit performance. The PMG and controls shall be capable of sustaining
circuit performance. The PMG and controls shall be capable of sustaining
and regulating current supplied to a single phase or three phase fault at
approximately 300% of rated current for not more than 10 seconds.
D. The subtransient reactance of the alternator shall not exceed 12 percent
based on the standby rating of the generator set.
E. Space Heater – Alternator shall be provided with 120V, 100W max. space
heater interlocked with generator run relay.
2.03 COOLING SYSTEM
A. Radiator – An engine mounted radiator with blower type fan shall be sized
to maintain safe operation at 122 degrees Fahrenheit maximum ambient
temperature.
B. The engine cooling system shall be pretreated by the Engine Supplier for
the inhibiting of internal corrosion.
C. The radiator shall exhaust through the building.
2.04 EXHAUST SYSTEM
A. The engine exhaust system shall be installed to discharge combustion
gases quickly and silently with minimum restriction. The exhaust system
including the generator exhaust silencer shall be designed for minimum
restriction and in no case shall the total exhaust system (including piping
system as installed) backpressure restriction imposed on the engine at full
operating load exceed the engine manufacturer’s maximum allowable
exhaust backpressure.
B. All exhaust piping shall be Schedule 40 heavy walled steel piping. The
generator exhaust muffler and all exhaust piping located within the
generator room shall be covered with appropriate insulation and shielding.
Piping shall be installed with 16 inches minimum clearance from
combustible materials.
C. The generator exhaust silencer shall be installed inside of the generator
room and exhaust piping terminated as shown on the Contract Drawings.
The exhaust silencer and associated piping shall be installation supported