Specifications
16201-3
L:\wpb_\wpb_emp1\W1200.13\p.m. Project #1\SECTION 16201-Indoor Generator and ATS.doc
10. Legends for all devices on all diagrams.
11. Sequence of operation, explanations of all portions of schematic
wiring diagrams.
12. Provide load calculations including starting and running kVA.
13. Transient voltage response calculation, no voltage transient shall
dip below 25%.
D. The specified kW shall be for continuous electrical service during
interruption of the normal utility source. These ratings must be
substantiated by manufacturer’s standard published curves. Special
ratings or maximum ratings are not acceptable.
E. O&M Manuals
1. Refer to the General Requirements.
F. Warranty
1. The Installing Contractor shall be responsible to generate and
provide to the Engineer scaled layout Drawings of the generator
room clearly depicting detailed dimensions of the mechanical
installation of all generator equipment including generator set,
vibration isolators, day tank and associated piping, exhaust flex
and muffler and associated piping as intended to be physically
located and installed within the generator room. Include detailed
and dimensioned elevation Drawings depicting the installation
mounting height of all equipment and piping, including the exhaust
system with the required insulation system installed within the
generator room. The scaled installation Drawings provided shall
indicate satisfactory installation and appropriate clearances for all
installed equipment and piping systems.
1.05 WARRANTY
A. Equipment furnished under this section shall be guaranteed against
defective parts and workmanship under terms of the manufacturer’s and
dealer’s standard warranty for a period of no less than five (5) years from
the date of the Owner’s acceptance of the unit.