Specifications

16201-2
L:\wpb_\wpb_emp1\W1200.13\p.m. Project #1\SECTION 16201-Indoor Generator and ATS.doc
1.03 CODES
A. All equipment shall be provided per the requirements of the following
codes as applicable for the intended use and installation:
1. NFPA 70, latest edition (National Electrical Code).
2. NFPA 110, Emergency and Standby Power Systems, latest edition.
3. UL 2200, the complete generator set shall be UL listed.
B. Emissions
1. Supplier shall be responsible to meet all EPA and other similar
codes.
1.04 SUBMITTALS
A. Submittals for approval shall be provided for any and all materials. No
materials shall be used without approval from the Engineer
B. Refer to the General Requirements for documentation of Shop Drawings
and O&M Manuals.
C. Provide additional submittal information:
1. Engine manufacturer, model number, power output parameters,
Drawings and elevations of the units, entrance points for power,
control, fuel, storage and foundation requirements.
2. Engine Generator/Exciter control cubical.
3. Fuel consumption rate curves at ¼, 2/4, ¾, 4/4 loads.
4. Exhaust mufflers and vibration isolators.
5. Battery charger, batteries and battery racks.
6. Diesel Storage Tank, day tank and fuel connection points.
7. Cooling water requirements of radiator.
8. Engine cooling air requirements and radiator fan capacity.
9. Electrical diagrams including schematic and interconnection
wiring diagrams for all equipment to be provided.