1. Two coats Series 113 H.B. Tnemec-Tufcoat water base acrylic epoxy. Apply at a minimum
rate of 120-170 square feet per gallon.
D. Gypsum Drywall
1. One coat Tnemec-cryl Sealer (thinned 10%). Apply at a minimum rate of 400 square feet per
gallon.
2. One coat Series 113 H.B. Tneme-Tufcoat water-base acrylic-epoxy. Apply at a minimum
rate of 120-170 square feet per gallon. Two coats will be required if applied by roller.
E. Carbon Steel, Ductile Iron, or Cast Iron
1. Prime coat Tnemec Series N69-1211 Epoxoline Primer epoxy-polyamide, 3-5 mils DFT.
2. Finish coat Tnemec Series N69 Hi-Build Epoxoline II epoxy-polyamide, 4-6 mils DFT.
F. Fuel Oil Tanks
1. Prime coat Series 61-5002 Tneme-Liner high solids catalyzed epoxy, 8-12 mils DFT.
2. Finish coat Series 61-5001 Tneme-Liner high solids catalyzed epoxy, 8-12 mils DFT.
G. Galvanized Steel and Other Non-Ferrous Metals
1. One coat Tnemec Series N69 Hi-Build Epoxoline epoxy-polyamide, 4-6 mils DFT.
H. PVC Piping
1. Two coats Tnemec Series N69 Hi-Build Epoxoline epoxy-polyamide. Apply at a minimum
rate of 300 square feet per gallon per coat.
I. Shop Finished Electrical and Mechanical Equipment
1. One coat Tnemec Series 27 F/C/ Tu[ppxu (Fast Cire E[pxu), 2-6 mils DFT.
2. One coat Tnemec Series N69 Hi-Build Epoxoline epoxy-polyamide, 4-6 mils DFT.
J. Wood Trim and Doors - Painted
1. Prime coat of Tenemec Series 10-99 W Tnemec primer applied at 2.5 mils DFT (350±
SF/Gal)..
2. Two coats of Tnemec Series 23 Enduratone (Semi-Gloss Alkyd Ename) applied at 2.0 mils
DFT per coat.
3.08 COATING SYSTEMS - EXTERIOR SURFACES
A. Carbon Steel, Ductile, or Cast Iron
1. Prime coat Tnemec Series 135 (Chembuild Surface Tolerant Epxy), 3-5 mils DFT.
2. Finish coat Tnemec Series 73 Endura-Shield III high build acrylic polyurethane, 2-5 mils
DFT.
B. Galvanized Steel and Other Non-Ferrous Metals
1. Prime coat Tnemec Series N69 Hi-Build Epoxoline epoxy-polyamide, 2-3 mils DFT.
2. Finish coat Tnemec Series 73 Endura-Shield III high build acrylic poly- urethane, 2-5 mils
DFT.
C. Above Ground Fuel Storage Tanks
1. Shop Primer: One coat Series 90-97 Tneme-Zinc zinc-rich urethane, 2.5-3.5 mils DFT.
2. Field Touch-Up: Series 90-97 Tneme-Zinc, 2.5-3.5 mils DFT.