Specifications
EDITORIAL REVISION PIP ELSWC07
February 2006 Shielded Power Cable Specification (5 to 46 kV)
Process Industry Practices Page 7 of 7
i. Descriptive literature (catalogs, etc.)
4.4.2 Documentation at Time of Shipping
The following information shall be provided to the purchaser:
a. Certified test reports at time of shipment
b. X-Y plot of the partial discharge test, supplied within 2 weeks after
shipment
4.5 Conflict Resolution
Any conflicts between the referenced documents shall be identified in writing to the
purchaser for resolution. In general, if resolving conflicts, the following order of
precedence shall apply:
a. Purchase order
b. PIP ELSWC07D Data Sheet
c. This Practice, PIP ELSWC07
d. Other referenced standards