February 2006 Shielded Power Cable Specification (5 to 46 kV)
Process Industry Practices Page 5 of 7
4.1.8 Armor Assembly
If specified on the purchaser’s PIP ELSWC07D Data Sheet, ICEA S-93-639-
2000, Section 7.3, Division I-type protective armor shall be provided for
multiple conductor cables. The armor shall be in accordance with UL 1569
for Type MC cables.
4.1.9 Outer Jacket
4.1.9.1 Unless otherwise specified on the purchaser’s PIP ELSWC07D Data
Sheet, an outer protective PVC jacket shall be applied over the
completed cable assembly.
4.1.9.2 Jacket shall be in accordance with ICEA S-93-639-2000, Section 7.1.
4.1.9.3 Unless otherwise specified on the purchaser’s PIP ELSWC07D Data
Sheet, jacket color shall be manufacturer’s standard.
4.1.9.4 Jacket shall be oil-resistant and sunlight-resistant in accordance with
UL 1072.
4.1.10 Cable Flame Rating
Unless otherwise specified on the purchaser’s PIP ELSWC07D Data Sheet,
cable shall be flame-retardant and shall meet or exceed the testing
requirements of IEEE 1202.
4.1.11 Cable Identification
The cable shall be marked and identified in accordance with NEC,
Article 310.11. Cables shall be NEC Type MV, marked “Sunlight Resistant,”
“For Use in Cable Tray,” and for “Direct Burial” in accordance with
UL 1072.
4.1.12 Cable Length Tolerance
Unless otherwise specified on the purchaser’s PIP ELSWC07D Data Sheet,
the tolerance for the length of each segment of cable shall be minus 0% to
plus 2%.
4.2 Inspection and Testing
4.2.1 Factory inspection and testing shall be performed on all cables in accordance
with the following standards:
a. ICEA S-93-639-2000, Section 9
b. IEEE 1202
c. UL 1072
4.2.2 If specified on the purchaser’s PIP ELSWC07D Data Sheet, optional testing
as defined by the purchaser shall be performed.