Specifications

Maxiva ULX Series
November 11, 2013
223
8882628300 WARNING:Disconnectprimarypowerpriortoservicing.
Copyright©2013,HarrisBroadcast
STEP 2 Closelyexaminethewaterthatwasdrainedfromthesystem.Ifitisrelatively
clean,proceedtofillthesystemwiththeglycol/distilledwatermixture.Ifitis
dirtyanotherfillandflushwithwatermaybeneeded.Systemsthatare
extremelydirtymayneedadditionalflushingwithacleaningsolution.
STEP 3 Endofprocedure.
2.12.5 CoolingSystemCleaning
STEP 1 Completelydrainthewaterfromthesystem.
STEP 2 Createcleansingsolution.Usingamixtureofdistilledwaterandacleaning
solution(amixtureof1cupofatrisodiumphosphatebased(lowsuds)
detergent,suchasCascade,thoroughlymixedin2gallonsofwarmwater),
proceedwiththefollowingsteps.
STEP 3 Pourthecleaningsolutionthroughaporouscloth(tofilteroutclumpsof
detergent)intothecontainer(reservoir)ofcleandistilledwaterandmix
thoroughlytocompletelydissolvealldetergent.
Note
In cold environments the effectiveness of the cleaning mixture is enhanced if it is heated. Heating can be
accomplished by installing a propane heater underneath the heat exchanger and temporarily enclosing
the unit with a tarp to heat up the cleaning mixture as it circulates cleaner solution through the exchanger.
STEP 4 Usethechargepumporcirculatingpumptofillthesystemwiththecleaning
solution.Monitorthesightglasstoconfirmfluidlevelandlackofairbubblesto
confirmcharg e.
STEP 5 Runthesystemfor40minutes.AlternatepumpsAandBfor20minuteseach.
STEP 6 Turnoffpump.Closebypassvalveandfullyopencabinetintakeandoutlet
valvestoallowcleaningsolutiontoflowthroughtransmittercabinet.
STEP 7 Runthesystemforanadditional20minutes.AlternatepumpsAandBfor10
minuteseach.Noteflowrateofsystem.
STEP 8 Drainthesystem.Todrainthesystemopenthedrainhosesandthesystem
ventvalves.Oncedrainingiscompleteclosealldrainandventvalves.
STEP 9 Disposeofcleaningsolutionincontainerandrinse.Refillthecontainerwith
cleandistilledwater.
STEP 10 Cleanthestrainerscreen.
STEP 11 Endofprocedure.
2.12.6 CoolingSystemFlushing
Flushthesystemtoremovethecontaminatedwaterbeforetheinitialtransmitteroperation.Beforechargingthe
systemwiththeglycol/watermixtureitmustbepurgedofallcleaningsolutionresidue.
Theflushingisaccomplishedbyalternatelyfilling,runninganddrainingthesystem,twotofour(ormoreifneeded)
timesusingdistilledwater.Thefollowingstepsoutlinetheflushingprocess.
Note
The length of flushing time and number of fill/drain cycles needed to achieve desired water quality will
vary with system size and the amount of residual (trapped) liquid in the system. Residual liquid is trapped
in the system and cannot be removed when the system is drained. Smaller systems with less residual liquid
may require a lower number of flush cycles.