Specifications

Maxiva ULX Series
November 11, 2013
211
8882628300 WARNING:Disconnectprimarypowerpriortoservicing.
Copyright©2013,HarrisBroadcast
2.8.1 SafetyGround
AsafetygroundwireisrequiredforeachACmainsinputandtheyshouldbeconnectedtothecoppergroundstud
showninFigure22.Thegroundingstudonthispanelisdirectlyattachedtothegroundstrapthatrunsfromthe
groundingblocklocatedonthecabinettoptothegroundblocklocatedinsidetherearofthecabinetonthefloor.
Figure 2-2 Safety Ground Connections Inside Cabinet (rear)
TheMaxivaULXSeriestransmittersrequire3phase208/220/240Vacor3phase380/400/415Vacat50/60Hz.Voltage,
frequencyandconfiguration(DeltaorWYE)shouldbeidentifiedatthetimeorderisplaced.
Caution
IF VOLTAGE VARIATIONS IN EXCESS OF ±10% ARE ANTICIPATED, THE AC
MAINS INPUT MUST BE EQUIPPED WITH AUTOMATIC VOLTAGE
REGULATORS (OPTIONAL EQUIPMENT) CAPABLE OF CORRECTING THE
MAINS VOLTAGE.
2.8.2 ACConnectionsProcedure
Note
It is important that the correct voltage, frequency and connection type be applied as the MOV (metal oxide
varistor) board components/ jumpers, IPA backplane jumpers, and PA backplane jumpers are configured
differently for delta or wye inputs.
STEP 1 RoutetheprimaryACconduit(s)throughclampsatthetopofthetransmitter
cabinet.
Thetopofthetransmittercabinethasprecutholesforclampstosecure
conduittothecabinetasshownintheoutlinedrawing.
Note
For the following two steps the access cover at the top of the transmitter and the panel covering the circuit
breakers in the top rear of the transmitter should be removed to facilitate connection of the AC mains to
the transmitter.
STEP 2 ConnecttheACwirestotheprimaryACterminalblocksCB23andCB24(for
higherpowerlevelstwoACinputsarerequired).Refertothewiringdiagram
fordetailsonspecificpowerlevels.TheACinputwireswillconnecttoCB23
andCB24locatedbehindtheaccessplateontop
rearofthecabinet(another
SafetyGround
Connections
ACMains
Connections