Baud Se ngs: selects the communica on baud rate between the LOE and the
a ached Modbus sensors. Refer to the Modbus sensors documenta on for
the appropriate se ng (typically 9600 Baud).
Number of Sensors On Line: sets the number of Modbus sensors that are con-
nected to the LOE.
Sensor Number to View: used to select the sensor number to be viewed or
programmed (also see “New Sensor Number” below). The parameters of the
selected sensor will populate the RS-485 Modbus Input pages, and the sensors
readings can be viewed in the RS-485 Holding Register page.
New Sensor Number: used to change the sensor number of the sensor cur-
rently being viewed (see “Sensor Number to View” above). Each Modbus sen-
sor connected to the LOE must be assigned a unique sensor number (0 to 10).
Duplicate sensor numbers will cause errors in communica on.
Delay Between Call-in Times: sets the delay between cycles of querying all at-
tached Modbus sensors.
RS-485 Se ngs