user manual

IRU-2xx4/3xx4 Rev. A2, 11/08
24
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
STOP TRANSMIT SENSOR
Stop Transmit Sensor allows the user to identify a sensor and have it start
transmitting. This command controls a single sensor.
To have sensor number 1 stop transmitting, use the command structure;
Send
AAh Start Byte
01h, Sensor Number
21h Command
01h NA
00h NA
55h End Byte
START TRANSMIT BANK
Start Transmit Bank allows the user to identify a bank of sensors and have
them start transmitting. This command controls up to 10 sensors providing they
are all assigned to the same bank.
To have Bank number 1 begin transmitting, use the command structure;
Send
AAh Start Byte
00h, NA
22h Command
01h Bank Number)
00h NA
55h End Byte
STOP TRANSMIT BANK
Stop Transmit Bank (e) allows the user to identify a bank of sensors and have
them stop transmitting. This command controls up to 10 sensors providing they
are all assigned to the same bank.
To have Bank number 1 stop transmitting, use the command structure;
Send
AAh Start Byte
00h, NA
23h Command
01h Bank Number
00h NA
55h End Byte