MODE DESCRIPTION PARAMETERS
13 Begin Trip 2 Units = Mode 1
Range = 0 - 9999
Default = 3.50
Sets the Begin point for Trip 2 Relay Output.
MODE DESCRIPTION PARAMETERS
14 End Trip 2 Units = Mode 1
Range = 0 - 9999
Default = 4.50
Sets the End point for Trip 2 Relay Output.
MODE DESCRIPTION PARAMETERS
15 Trip 2 Type Range = 0 - 7
0 - near
1 - exclusive
2 - hysteresis near
3 - far
4 - inclusive
5 - hysteresis far
6 - disable
7 - loss of echo
Default = 0
Selects the output type for Trip 2.