user manual User guide

Rev. A3, 10/08 DCR-WEB
17
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Utilities
Temperature Compensation
As air temperature changes, so does the speed of sound. This change can
cause 0.18% drift in distance for every °C change. The TEMPCOMP Mode
allows compensation in the readings for this change. The DCR-WEB contains
an internal thermistor which measures temperature in °F. By turning temperature
compensation on, the effects of temperature changes will be reduced.
MODE DESCRIPTION PARAMETERS
TEMPCOMP Temperature Range = ON-OFF
Compensation Default = OFF
VIEWTEMP Displays Detected Range = -20 to +140
Temperature
Reset
If the mode adjustments get scrambled or if the factory preset values are
wanted, Change this mode to 1 and press M-UP or M-DN and all of the
parameters will be “RESET” to their factory defaults.
MODE DESCRIPTION PARAMETERS EXPLANATION
RESET Reset Range = 0,1
Calibration
Entering a 1 will RESET the
Controller to Factory
Defaults.