user manual Instruction Manual
Rev. A1, 2/14 DCR-1006A Ultrasonic Controller
7
Automaon Products Group, Inc.
APG...Providing tailored soluons for measurement applicaons
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
• Always mount above the highest ancipated target level by at least the
published minimum blanking distance. If a target enters into the blanking
area, error in the detecon will occur. It is always advisable to allow for
sucient headroom to ensure that the target does not enter the blanking
area.
• Generally it is advisable to mount the sensor away from any vessel ll
spouts. However, if heavy foam is expected, it is oen helpful to mount the
Sensor near a ll spout where the foam is being dispersed.
• Avoid mounng the sensor in the direct center of a tank with a signicantly
domed top. A domed top can act as parabolic dish, amplifying small
undesired signals that may be present inside the tank.
• Avoid mounng the sensor in close proximity to tank walls, especially on
tanks with corrugated walls or in applicaons where product buildup on
the tank walls may occur.
Low Sensivity Detecon Area High Sensivity Detecon Area