Relay Trip Types
NEAR:
Acvates whenever the reading is less than the Trip Value.
EXCLSV (Exclusive):
Acvates whenever the reading is less than the Trip Value or greater than the
Trip Value + Trip Window.
H NEAR (Hysteresis Near):
Acvates unl the reading exceeds the Trip Value + Trip Window, then
deacvates unl the reading falls below the Trip Value.
FAR:
Acvates whenever the reading is greater than the Trip Value.
INCLSV (Inclusive):
Acvates whenever the reading falls within the Trip Window.
H FAR (Hysteresis Far):
Acvates whenever the reading exceeds the Trip Value + Trip Window, and
remains acve unl the reading drops below the Trip Value. Once deacvated
the relay will remain inacve unl the reading once again exceeds the Trip
Value + Trip Window.
OFF:
Disables the relay.
LOE (Loss of Echo):
Holds the relay acve unless a loss of echo condion (no target detected)
occurs.
INPUT (Switched Input):
Acvates or deacvate the relay based on the state of the switched input
(closed or open).