user manual Instruction Manual

DCR-1006A Ultrasonic Controller Rev. A1, 2/14
24
Automaon Products Group, Inc.
APG...Providing tailored soluons for measurement applicaons
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
HCSPHE (Horizontal Cylinder with Hemispherical Ends)
Parameters:
FULL d (Full Distance)
EMPTYd (Empty Distance)
LENGTH (Tank Length)
dIAMET (Tank Diameter)
*ENd RA (End Radius)
*set to 0 for at ended tanks.
Diameter
Length
Empty
Distance
End
Radius
Full
Distance
SPHERI (Sphere)
Parameters:
FULL d (Full Distance)
EMPTYd (Empty Distance)
dIAMET (Tank Diameter)
Empty
Distance
Diameter
Full
Distance
L CALC (Linear Calculaon)
Applies a conversion mulplier to the level reading (based on the selected
Units; inches, feet, meters).
Example: suppose the product in a tank weighs 206.25 pounds per inch of
level. Assuming the Units are set to inches, the Mulplier would be 206.25
Parameters:
FULL d (Full Distance)
EMPTYd (Empty Distance)
L MULT (Mulplier)