user manual Instruction Manual
Rev. A1, 2/14 DCR-1006A Ultrasonic Controller
17
Automaon Products Group, Inc.
APG...Providing tailored soluons for measurement applicaons
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
SENSIT (Sensivity):
Controls the level of amplicaon applied the returning target echoes (signals).
The sensivity seng is expressed as a percentage; 0 to 100%.
PULSES:
Controls the number of sound wave pulses sent in each ultrasonic burst. The
greater the number of pulses, the stronger the transmied signal. Range: 0 to
20 pulses.
bLANK (Blanking):
Sets the distance, beginning at the sensor face, to the point where target signals
will be accepted. All targets closer than the blanking distance will be ignored.
The blanking should never be set to less than the minimum range specicaon
of the sensor. If the target enters the blanking area, reading errors will occur.
GAIN C (Gain Control):
Determines how the sensor applies gain to the returning target echoes.
Manual: Sensivity and Pules remain constant.
Autosense: the sensor connually adjusts the Pulses and Sensivity (within
the set parameter bounds) in order to opmize the signal strength.
*Hard Target: used for highly reecve targets. Targets echoes at close
range are amplied less.
*So Target: used for harder to detect targets. Targets at close range are
amplied more.
*So-Auto: autosense using the so target gain rate.
(*available with MNU sensors only)
AVERAG (Averaging):
Denes the number of target readings that will be averaged together to become
the displayed reading. Each qualied target reading (see Filter Window and
Out of Range Samples on next page) is placed into a rst-in, rst-out buer and
averaged with previous readings. A higher Averaging will result in smoother
readings, but will also slow the response to rapid changes in the target distance.