Installation manual

15
Installation
Recommended water diagram
(Fig. 9)
Typical water circuit diagram for Aeromax Plus unit
(see fig. 9)
1 Isolating valves
2 System filter
3 Expansion vessel with PRV & Gauge (Robokit)*
4 Flush & Fill Ports
5 System drain valve (at lowest point of system)*
6 Air purge (at highest points of system)*
7 3-way valve
8 Hot water cylinder
9 Heating system
10 Circulating pump with isolating valves*
11 Flowmeter/setter
*not included in installers pack
% Inhibited Propyl-
ene Glycol
10% 20% 30% 40%
Freezing time (*) -4 °C -9 °C -15 °C -23°C
Correction
Factors
Capacity 0,996 0,991 0,983 0,974
Absorbed power 0,990 0,978 0,964 1,008
Loss of head 1,003 1,010 1,020 1,033
(*) Note: Temperature values are indicative.
Always refer to the temperatures indicated for the specific product used
TABLE TO USE FOR CALCULATING THE WATER CONTENT IN THE SYSTEM
Installed Unit .............
Unit content (*) l .............
Pipe content (**) l .............
Uses (fan-coil, panels, radiators, etc.) (***) l .............
Total content (****) l .............
(*) Consult the technical data table.
(**) Consult the pipe water content table.
(***) Consult the manual from the relevant manufacturer.
(****) The water content of the system must be greater than the minimum value for units without hydronic kit. The minimum
value is necessary to provide optimal comfort.
Detailed installation schematics can be found at the back of the manual.
Should you require further technical assistance call your local office – details on the back page of this manual.
Do not use the heat pump to treat industrial process, swimming pool or sanitary water. In all these
cases, provide an intermediate heat exchanger.