Specifications

19
7.1 Codes
See boiler manual for information pertaining to installation
in State of Massachusetts.
System incorporates gas- red, direct vent, condensing
appliances and must be installed in accordance with the
following:
Fuel Gas:
United States: Installation shall conform to National
Fuel Gas Code (NFPA-54/ANSI Z223.1).
Canada: Installation shall be in accordance with CSA-
B149.1 and B149.2 installation codes.
Authority having jurisdiction
Electrical:
United States: National Electrical Code (ANSI/NFPA-
70).
Canada: CAN/CSA-C22.1 Canadian Electrical Code.
Authority having jurisdiction
Condensate Disposal:
Authority having jurisdiction
Installers:
Authority having jurisdiction
Follow recommended maintenance outlined in this
manual.
Grid Interconnection:
Authority having jurisdiction with respect to
interconnecting to grid.
7.2 System Sizing And Application
Select system with proper capacity before continuing
installation. Firing rate of system should be greater
than or equal to calculated peak heating load (heat
loss) for building or area(s) served by system. See
Section 2 for system ratings.
Base heat loss calculations on approved industry
methods.
Con gure hydronic
freewatt PLUS
System with Zone
2 operated by Smart Zone HAI thermostat supplied
with
freewatt PLUS
System. Zone 2, Smart Zone,
must have suf cient thermal load to provide proper
operation of MCHP unit. Too small of heat load in
Smart Zone will result in frequent MCHP cycling and
poor electrical power savings. The “Smart Zone” should
be selected as zone with largest heating demand (but
not domestic hot water zone). Normally, this would
be largest space heating zone on rst oor of two
story home.
freewatt PLUS
System will produce
best electric power generation bene t if Smart Zone
represents about 25% of total home heating load.
Consider combining zones to achieve desired heat
load for Smart Zone if there is no single large zone in
existing distribution system but many small zones.
freewatt PLUS
System must be applied with hydronic
heating systems having ample heat delivery capacity
relative to maximum or design heat load. This is
requirement for
freewatt PLUS
and all high-
ef ciency hydronic systems to achieve maximum
energy ef ciency. “Under-radiated” system requiring
high supply water temperature (above 180°F) during
outdoor low-temperature design conditions will result
in reduced contribution of MCHP to total heat delivery,
reducing electrical power production bene t. Preferred
design operating temperature is 160°F. Consider
adding additional heat radiation to existing under-
radiated distribution systems for proper application of
freewatt PLUS
.
Power generation performance of
freewatt PLUS
System may be adversely affected if there is any zone
resulting in constant active call for heat during heating
season (i.e., highly under-radiated zone). Verify all
zones have enough radiation, even during very cold
weather, so no zone thermostat will produce continuous
call for heat (i.e., cannot be satis ed).
freewatt PLUS
requires different ECR zone relay
controls depending on type of zoning utilized: zoned
by circulators, valves, or air handlers. Verify you
have correct ECR zone relay control before beginning
installation.
7 - BEFORE INSTALLING THE SYSTEM