Specifications

15
4 - APC UNIVERSAL TRANSFER SWITCH CONFIGURATION
Table 4-1 Typical UTS6H Circuit Setup without UPS
Typical UTS Circuit Setup without UPS
PARAMETER
CIRCUIT
I
CIRCUIT
2
CIRCUIT
3
CIRCUIT
4
CIRCUIT
5
CIRCUIT
6
Load Type
Other (con-
densate
pump)
Sump
pump
Boiler Computer
Security
System
Refrigerator
Source GEN GEN GEN GEN GEN GEN
Delayable Yes Yes (1) No Yes Yes Yes
Max time off (min) 30 1 30 5 60 30
Min time on (min) 30 2 30 5 60 15
Security Mode Off Off Off Off Off Off
Amp Rating(A) 15 15 15 15 15 15
Note (1)
Delayable - Yes:
Setting is required for Warm Air freewatt
PLUS
System boiler to prevent freewatt
PLUS
System
or sump pump from losing power when in Backup Mode. If sump pump and boiler may operate at same time (power out-
ages during heating season and heavy rain events), possible solutions include:
Battery-backed sump pumpA.
UPS and con gure sump pump power source as “Either” UPS or Generator.B.
Table 4-2 Typical UTS6H System Setup without UPS
Typical UTS6H System Setup without UPS
Bypass mode No
Load shedding? On
Voltage sensitivity Medium
Time Management On
Reset Energy Meter No
System Test No
Backup1 Source Type Generator
GEN power rating 1700 (1)
GEN SRGE Overload Time 0 seconds
GEN Start Mode manual
Backup2 Source Type none
GEN power rating 1800
GEN SRGE Overload Time 0 seconds
Reset to default no
NOTE:
(1) Available generator power is set to 1,700 watts to account for 100 watt power consumption of load balancing
transformer.