System information

APCrecommendsthatawholebatterymodule(onerowofbatteries)isreplacedatthesametimeto
ensureoptimalrun-time(seeExample1).Howeveritmayonlybenecessarytoreplacethreebattery
unitsatthesametimeaccordingtoExamples2and3inthetablebelow.
PositionAPositionBPositionCPositionDPositionEPositionF
Example1
NewNewNewNewNewNew
Example2
NewNewNew
OldOldOld
Example3
OldOldOld
NewNewNew
DirectionsforStorage
Note:Thebatterymodulesmustbestoredindoorsandwiththeirprotectivepackaging
stillinplace.
Note:Storedbatteriesshouldberechargedatregularintervals,dependingonthestorage
temperature.
StorageTemperature
RechargeInterval
-15°to20°C/5°Fto68°F9months
20°to30°C/68°Fto86°F6months
30°to40°C/86°Fto104°F3months
Caution:Donotstorethebatteriesformorethan12months.
990–2748E-001
SymmetraPX250/500kW400/480V
39