System information

PerformaBatteryRuntimeCalibration
Recalibratingthebatterieskeepsmeasurementslikeruntimeandbatterychargeaccurate.
1.GototheUserCongurationscreenbyfollowingthestepsin“AccesstheUserConguration
Screen“.
2.PresstheBatteryT estSettingsbuttonontheUserCongurationscreentoaccesstheBattery
TestSettingsscreen.
3.PressStarttobeginthebatteryruntimecalibration.Thebatteriesmustbe100%chargedtostart
acalibration.YoucanpressCanceltostopthecalibration.Thestatusoftheruntimecalibration
isshownunderRuntimecalibrationstatus.
SettheBatteryTestSettings
Thebatteryself-testsimulatesthebatterymodeofoperation.IfACutility/mainspowerfailsduringthe
test,theteststopsandtheUPSsuppliesbatterypower.
Thetestdetectsanyweakordefectivebatterycells.Todothis,theloadmustbehighenoughtodraw
sufcientcurrentwhichinturncausesthevoltagetodroptoalowlevel.
Thefollowingcriteriashouldbemettoensureyoursearchdetectsanyweakbatterycells:
Thetotaldischargecurrenttotheloadfromboththepositiveandnegativesidesofthebatteries
needstobeatleasthalfoftheratedbatteryAh,whichisdeterminedbythenumberofinstalled
batterystrings.Forexample,ifyouhave18Ahofbatteries,morethan9Amustbedrawnbythe
loadfromeachbatteryside.
Boththepositiveandnegativebatteryvoltagemustbelowerthan280Vforlongerthan16seconds.
26
SymmetraPX250/500kW400/480V
990–2748E-001