System information

3.PresstheNormalOp.StaticBypassbutton.
SingleSystemParallelSystem
4.PresstheInitiateTransferbuttontogotostaticbypassoperation.TheInitiateTransferbutton
isgreyedoutwhenthetransferisnotavailable.
5.CheckthatthestatushaschangedtoRequestedStaticBypassintheupperrightcorner.
TransferfromRequestedStaticBypasstoNormal
Operation
Note:Followingthisprocedurewilltransfertheentireparallelsystemfromrequested
staticbypasstonormaloperation.
Note:PressthehomebuttontogototheUPSSummaryorParallelSystemSummary
screen.
18
SymmetraPX250/500kW400/480V
990–2748E-001