Specifications

SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 10
Emergency Power Off (EPO)
The system power can be disabled in an emergency by closing a switch connected to the EPO.
Wiring must be performed by a qualified electrician. Adhere to all local and national electrical codes.
The switch should be connected in a normally open switch contact. External voltage is not required; the
switch is driven by 24 V internal supply. In closed condition, 4 mA of current are drawn.
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to
the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard
cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch.
CL2: Class 2 cable for general use.
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).
For installation in other countries: Use standard low-voltage cable in accordance with national and
local regulations.
EPO terminal
located on rear panel
EPO connector
Strip insulation from one end of each wire to be used for
connecting EPO.
Insert screwdriver into the slot above terminal to be
wired. Insert stripped wire into terminal. Remove
screwdriver to secure wire in terminal. Repeat for each
terminal.
su0158a