Specifications
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 17
Start-Up
Connect battery modules
Connect all eight battery modules. Failure to do so may cause equipment damage.
Replace battery compartment doors.
Tighten the screws to secure battery compartment doors.
Install bezels
There is a single latch on either side of the UPS bezel.
There are two latches on either side of the battery
pack and XLBP bezels.
Connect load to UPS
Connect equipment to the UPS. Refer to “Output wiring” on page 14.
Each connected load must be switched OFF.
The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full
battery run capability during this initial charge period.
Refer to the APC Web site, www.apc.com for battery runtimes.
Where appropriate use an APC extension battery cable. For ordering details contact a dealer or APC
through the Web site www.apc.com.
Connect power to UPS and load
1. Connect input power to UPS.
2. Check the display interface LCD for messages.
3. Turn on the load using the interface display menu option, Turn Load On accessed through the
Control menu screen. Refer to “Menu Tree” on page 20 and “Menu screens map” on page 23.