Specifications
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 16
Connect PDU to output wiring tray
1. Remove the five screws securing the strain
relief bar on the output wiring tray.
2. Connect the PDU on the external battery pack
to the output wiring tray.
3. Replace the strain relief bar using the five
screws removed in step 1.
4. Replace the covers using the screws removed
preciously.
Connect the load using external battery pack connectors
The PDU must be connected to the output
wiring tray. Refer to “Connect PDU to output
wiring tray” on page 16.
Connect the load to the UPS using the six
output receptacles on the external battery
pack. Connect the external battery pack to the
UPS.
Connect the ground wire between the UPS
and the external battery pack.
Connect the external battery pack to the UPS
by plugging the external battery pack
connectors into the UPS rear panel
connectors.
Refer to the external battery pack user
manual for details on removing and securing
the battery connector safety covers.
su0156b
5x
su0169a
Output wiring tray
External battery pack with
PDU and six output
receptacles
Strain relief bar
su0345a
UPS
External battery
pack
Six output connectors
Ground wire