Specifications

SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 11
Wiring Specifications
Wire gauges may vary. Adhere to national and local electrical codes when wiring this unit.
* Terminal screw tightening torque: 40 lb-in (4.5 N-m)
Acceptable input frequency range is 40 to 70 Hz.
Output voltage and frequency are user selectable only when UPS is in Load Disconnect mode.
Refer to display interface menu screens for available options.
Input Connections Output Connections
Utility Input
Wire to L1, N/L2, ground
Hardwire
Wire to L1, N/L2, ground
PDU
XL battery pack PDU to UPS: Wire L1, N/L2, ground
System Wiring Voltage Current
Full Load
(maximum)
External Input Circuit
Breaker
(typical)
Wire Size
(typical)*
SURT14K
Input 200 Vac 80 A 100 A / 2-pole 25 mm
2
(2 AWG)
Output 200 Vac 70 A not required 25 mm
2
(2 AWG)
SURT15K
Input 208/240 Vac 80 A 100 A / 2-pole 25 mm
2
(2 AWG)
Output 208/240 Vac 72 A not required 25 mm
2
(2 AWG)
SURT18K
Input 200 Vac 100 A 125 A / 2-pole 35 mm
2
(1 AWG)
Output 200 Vac 90 A not required 35 mm
2
(1 AWG)
SURT20K
Input 208/240 Vac 100 A 125 A / 2-pole 35 mm
2
(1 AWG)
Output 208/240 Vac 96 A not required 35 mm
2
(1 AWG)