User manual
SURT192RMXLBP2/SURT192RMXLBP2J User Manual 4
Accessories
Install accessories prior to connecting power to the UPS.
Refer to the APC Web site, www.apc.com for available accessories.
Specifications
Environmental Specifications
Physical Specifications
Temperature
Operating 0° to 40° C (32° to 104° F) This unit is intended for indoor use
only. Select a location sturdy
enough to handle the weight.
Do not operate unit where there is
excessive dust or temperature or
humidity are outside specified
limits.
Environmental factors impact
battery life. High temperatures, poor
utility power, and frequent, short
duration discharges will shorten
battery life.
Storage -15° to 30° C (5° to 86° F)
charge UPS battery every six months
30° to 70° C (86° to 158° F)
charge UPS battery every three months
Maximum
Elevation
Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity
0 to 95% relative humidity,
non-condensing
Weight
Refer to the Safety Guide supplied with this unit for lifting guidelines.
Battery Pack with eight battery modules 181 kg (400 lbs)
without battery modules 44 kg (96 lbs)
each battery module 17 kg (38 lbs)
Maximum number of external battery packs (XLBPs)
10
Combined weights of UPS, battery pack and
all XLBPs installed in a rack must not exceed
rack weight limits.
Dimensions
Battery Pack
width
482 mm (19 in) with rack-mount brackets
432 mm (17 in) without rack-mount brackets
height
263 mm (10 in)
depth
739 mm (29 in) with PDU
720 mm (28 in) without PDU